6-14
Close and Reclose Logic
Date Code 20020215
SEL-351R Instruction Manual
If the reclosing relay is defeated, the following also occur:
•
All three reclosing relay state Relay Word bits (79RS, 79CY, and 79LO) are forced to
logical 0 (see Table 6.1).
•
All shot counter Relay Word bits (SH0, SH1, SH2, SH3, and SH4) are forced to
logical 0 (the shot counter is explained later in this section).
•
The front
-
panel LEDs RS, CY, and LO are all extinguished—a ready indication that the
recloser is defeated.
Close Logic Can Still Operate When the Reclosing Relay is Defeated
If the reclosing relay is defeated, the close logic (see Figure 6.1) can still operate if SEL
OGIC
control equation circuit breaker status setting 52A is set to something other than numeral 0.
Making the setting 52A = 0 defeats the close logic and also defeats the reclosing relay.
For example, if 52A = IN101, a 52a circuit breaker auxiliary contact is connected to input
IN101. If the reclosing relay does not exist, the close logic still operates, allowing closing to
take place via SEL
OGIC
control equation setting CL (close conditions, other than automatic
reclosing). See
earlier in this section for more discussion on SEL
OGIC
control
equation settings 52A and CL. Also see
Optoisolated Inputs
in
Section 7: Inputs, Outputs,
Timers, and Other Control Logic
for more discussion on SEL
OGIC
control equation setting
52A.
Reclosing Relay Timer Settings
The open interval and reset timer factory settings are shown in Table 6.2:
Table 6.2: Reclosing Relay Timer Settings and Setting Ranges
Timer
Setting (range)
Factory Setting
(in cycles)
Definition
79OI1 (0.00–999999 cyc)
300.00
open interval 1 time
79OI2 (0.00–999999 cyc)
600.00
open interval 2 time
79OI3 (0.00–999999 cyc)
600.00
open interval 3 time
79OI4 (0.00–999999 cyc)
0.00
open interval 4 time
79RSD (0.00–999999 cyc)
1800.00
reset time from reclose cycle state
79RSLD (0.00–999999 cyc)
600.00
reset time from lockout state
The operation of these timers is affected by SEL
OGIC
control equation settings discussed later
in this section. Also, see the settings sheets at the end of
Section 9: Setting the SEL-351R
Recloser Control
.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......