Date Code 20020215
Close and Reclose Logic
6-1
SEL-351R Instruction Manual
SECTION 6: CLOSE AND RECLOSE LOGIC
This section is made up of three subsections:
Close Logic
This subsection describes the final logic that controls the close output (e.g., RCCL =
CLOSE). This output closes the recloser for automatic reclosures and other close
conditions (e.g., manual close initiation via serial port or optoisolated inputs).
If automatic reclosing is not needed, but the SEL-351R Recloser Control is to close
the circuit breaker for other close conditions (e.g., manual close initiation via serial
port or optoisolated inputs), then this subsection is the only subsection that needs to be
read in this section (particularly the description of SEL
OGIC
®
control equation setting
CL).
Reclose Supervision Logic
This subsection describes the logic that supervises automatic reclosing when an open
interval time times out—a final condition check right before the close logic asserts the
close output contact.
Reclose Logic
This subsection describes all the reclosing relay settings and logic needed for
automatic reclosing (besides the final close logic and reclose supervision logic
described in the previous subsections).
The reclose enable setting, E79, has setting choices N, 1, 2, 3, and 4. Setting E79 = N
defeats the reclosing relay. Setting choices 1 through 4 are the number of desired
automatic reclosures.
Note:
Setting E79 = N defeats the reclosing relay, but does not defeat the ability of
the close logic described in the first subsection (Figure 6.1) to close the circuit
breaker for other close conditions via SEL
OGIC
control equation setting CL
(e.g., manual close initiation via serial port or optoisolated inputs).
C
LOSE
L
OGIC
The close logic in Figure 6.1 provides flexible circuit breaker closing/automatic reclosing with
SEL
OGIC
control equation settings:
52A (breaker
status)
CL
(close conditions, other than automatic reclosing)
ULCL
(unlatch close conditions, other than circuit breaker status, close failure, or
reclose initiation)
and setting:
CFD
(Close Failure Time) See the settings sheets in
Section 9: Setting the SEL-351R
Recloser Control
for setting ranges.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......