13-6
Testing and Troubleshooting
Date Code 20011205
SEL-311A Instruction Manual
Testing Via Sequential Events Recorder
You can set the relay to generate an entry in the Sequential Events Recorder (SER) for testing
relay elements. Use the
SET R
command to include the element(s) under test in any of the SER
trigger lists (SER1 through SER3). See
Section 12: Standard Event Reports and SER
.
To test the phase time-overcurrent element 51PT with the SER, make the following setting:
SER1 = 51P 51PT
Element 51P asserts when phase current is above the pickup of the phase time-overcurrent
element. Element 51PT asserts when the phase time-overcurrent element times out. The
assertion and deassertion of these elements is time-stamped in the SER report. Use this method
to verify timing associated with time-overcurrent elements, reclosing relay operation, etc. Do not
forget to reenter the correct relay settings when you are ready to place the relay in service.
R
ELAY
T
ESTING
Use this section as a guide to test overcurrent, distance, and negative-sequence directional
elements in the SEL-311A, SEL-311B, and SEL-311C Relays. Note that the SEL-311A has two
zones, the SEL-311B has three zones, and the SEL-311C has four zones. Settings E21P,
E21MG, and E21XG will need to be set to “2” instead of “3” when testing the SEL-311A.
Equipment Required
The following equipment is necessary for initial checkout.
1. Source of control power.
2. Source of three-phase voltages and at least two currents.
3. Ohmmeter or contact opening/closing sensing device.
Checkout Procedure
Step 1.
Purpose: Be sure you received the relay in satisfactory condition.
Method: Inspect the instrument for physical damage such as dents or rattles.
Step 2.
Purpose: Refer to the Relay Part Number and Hardware Identification Sticker on the
relay rear panel to verify the power supply voltage, dc control voltage, and nominal
ac signal magnitudes appropriate for the relay under test.
Method: Refer to the information sticker on the rear panel of the relay.
The Power options include 24 volts dc, 48 volts dc, and 250 volts ac/dc. Refer to the
sticker attached to your relay to determine the magnitude of voltage you should
apply to the relay power supply input terminals. The voltage source should be
capable of providing 12 watts continuously at the rated voltage.
The Logic Input options include 24 volts dc, 48 volts dc, 110 volts dc, 125 volts dc,
220 volts dc, and 250 volts dc. To assert a relay logic input, apply dc voltage to the
relay input terminals. Refer to the sticker attached to your relay to determine the
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......