Date Code 20011205
Inputs, Outputs, Timers, and Other Control Logic
7-5
SEL-311A Instruction Manual
L
OCAL
C
ONTROL
S
WITCHES
The local control switch feature of this relay replaces traditional panel-mounted control switches.
Operate the sixteen (16) local control switches using the front-panel keyboard/display (see
Section 11: Front-Panel Interface
).
Figure 7.3: Local Control Switches Drive Local Bits LB1 Through LB16
The output of the local control switch in Figure 7.3 is a Relay Word bit LB
n
(
n
= 1 through 16),
called a local bit. The local control switch logic in Figure 7.3 repeats for each local bit LB1
through LB16. Use these local bits in SEL
OGIC
control equations. For a given local control
switch, the local control switch positions are enabled by making corresponding label settings.
Note:
On SEL-311A Relays without an LCD, the Relay Word bits LB1–LB16 are
always = logical 0. (Local bit control is not possible because there are no
front-panel buttons or display on the relay.)
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......