Date Code 20011205
Breaker Monitor and Metering Functions
8-29
SEL-311A Instruction Manual
Maximum/Minimum Metering Updating and Storage
The SEL-311A Relay updates maximum/minimum values, if the following conditions are met:
·
SEL
OGIC
control equation setting FAULT is deasserted (= logical 0).
The factory default setting is set with time-overcurrent and distance element pickups:
FAULT = 51G + M2P + Z2G
If there is a fault, these elements pick up and block updating of maximum/minimum
metering values.
·
The metering value is above the previous maximum or below the previous minimum for
2 cycles.
·
For voltage values, the voltage is above 13 V secondary.
·
For current values, the currents are above:
0.25 A secondary {5 A nominal}
0.05 A secondary {1 A nominal}
·
Megawatt and megavar values are subject to the above voltage and current thresholds.
The SEL-311A Relay stores maximum/minimum values to nonvolatile storage once per day (it
overwrites the previous stored value if it is exceeded). Should the relay lose control power, it
will restore the maximum/minimum values saved by the relay at 23:50 hours on the previous day.
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......