B-4
Firmware Upgrade Instructions
Date Code 20011205
SEL-311A Instruction Manual
If this occurs, press
<ENTER>
to see if the level 0 prompt “ = ” appears on your
terminal screen. If it does, enter Access Level 2 by issuing the
ACC
and
2AC
commands and proceed to self-test failure: IO_BRD, Step 12a.
If the relay does not display the level 0 “ = ” prompt, the Relay baud rate has changed
back to the factory default of 2400 baud; go to self-test failure: CR_RAM, EEPROM,
and IO_BRD, Step 12e.
Self-test failure: IO_BRD
a. Issue the Initialize (
INI
) command to reinitialize the I/O Board(s). If this
command is not available, go to Step 12e.
b. Answer
Y
<ENTER>
to the question: “Are the new I/O board(s) correct
(Y/N)” After about one minute, the EN LED will illuminate. The original
relay settings have been retained, but should be checked for accuracy.
c. Enter Access Level 2 by issuing the
ACC
and
2AC
commands. Go to Step 13.
Self-test failure: CR_RAM, EEPROM, and IO_BRD
d. Set your communications software settings to 2400 baud, 8 data bits, 1 stop
bit. Now enter Access Level 2 by issuing the
ACC
and
2AC
commands, (the
factory default passwords will be in effect: OTTER for level 1, TAIL for
level 2).
e. Issue the Restore Settings (
R_S
) command to restore the factory default
settings in the relay. This takes about two minutes, then the EN LED will
illuminate.
Note:
If the relay asks for a part number to be entered, use the number from
the label on the firmware diskette, or from the new part number sticker
(if supplied).
f. Enter Access Level 2 by issuing the
ACC
and
2AC
commands, (the factory
default passwords will be in effect: OTTER for level 1, TAIL for level 2).
g. Restore the original settings as necessary, using the SEL-5010 Settings
Assistant, or with each of the following commands:
SET G
,
SET 1
,
SET L 1
,
SET 2
,
SET L 2
,
SET 3
,
SET L 3
,
SET 4
,
SET L 4
,
SET 5
,
SET L 5
,
SET 6
,
SET L 6
,
SET P 1
,
SET P 2
,
SET P 3
,
SET P F
,
SET R
.
h. Set the original relay passwords saved in Step 3 via the
PAS
command.
For
example,
PAS 1:APPLE <ENTER>
sets the level 1 password to APPLE.
Use a similar format for
PAS B
and
PAS 2
. The
PAS
command is case-
sensitive, so the lower and upper case letters are treated differently.
If there are still any FAIL codes on the Relay LCD, see
Section 13: Testing and
Troubleshooting.
13. Verify the calibration settings by issuing the
SHO C
command. If the settings do not
match the settings recorded in Step 3, reissue the settings with the
SET C
command.
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......