Date Code 20011205
Testing and Troubleshooting
13-31
SEL-311A Instruction Manual
Step 1.
Execute the
SHOWSET
command and verify the following relay settings: Z1MAG,
Z1ANG, PMHOZ, Z2P, 50PP2, Z2F, and 50QF. The example relay settings use the
following settings: Z1MAG = 7.8; Z1ANG = 83.97°; PMHOZ = 3; Z2P = 9.36
W
;
50PP2 = 2.22; Z2F = 0.77
W
; 50QF = 0.5 amps secondary.
Execute the
SET
command and change the example ELOP setting from Y to N. This
prevents the relay Loss-of-Potential logic from blocking operation of the relay
distance elements.
Step 2.
Select an output contact to indicate operation of the M2P element. In this example
we use the OUT106 output.
From Access Level 2, execute the
SET L n
command to configure Output 6 to close
for assertion of the M2P element.
=>>SET L 1 OUT106 <ENTER>
SET L 1 OUT106 <ENTER>
SET L 1 OUT106 <ENTER>
SET L 1 OUT106 <ENTER>
SELogic group 1
OUT106 =0
? M2P <ENTER>
M2P <ENTER>
M2P <ENTER>
M2P <ENTER>
OUT107 =0
? END <ENTER>
END <ENTER>
END <ENTER>
END <ENTER>
After you type
END <ENTER>
to end the set procedure, the relay displays the
current logic settings. Type
Y <ENTER>
to accept those settings.
Connect output OUT106 to the sense input of your test set, an ohmmeter, or some
other contact sensing device.
Step 3.
Connect the voltage sources to the relay A-phase, B-phase, and C-phase voltage
inputs. Connect the current source to the relay B-phase and C-phase current inputs.
Refer to the voltage and current connections shown in Figure 13.6 as an example.
Step 4.
Select the magnitude of the test signals, I
BC
, V
B
, and V
C
.
Table 13.3 summarizes the test quantities for the Zone 2 B-C phase distance element
based upon the example relay settings.
Table 13.3: Test Quantities for Zone 2 Phase Distance Element
Test Voltages
Test Current
V
A
= 67
Ð
0° volts
I
TEST
= 2.5
Ð
-173.97° amps
V
B
= 46.8
Ð
-150° volts
V
C
= 46.8
Ð
150° volts
The following text describes a hand calculation method you may use to calculate
relay distance element voltage and current test signals. If you do not wish to review
this information, go to Step 5.
The relay phase distance elements operate based upon the magnitude of applied
phase-to-phase impedance. The impedance calculation is also supervised by the
functions described. To effectively test the distance elements, select voltage and
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......