Date Code 20011205
Inputs, Outputs, Timers, and Other Control Logic
7-33
SEL-311A Instruction Manual
Factory Settings Example
In the factory SEL
OGIC
control equation settings, four output contacts are used:
OUT101 = TRIP
(overcurrent tripping/manual tripping; see
Section 5: Trip and
Target Logic
)
OUT102 = TRIP
OUT103 = CLOSE
(automatic reclosing/manual closing; see
Section 6: Close Logic
)
·
·
·
OUT107 = 0
(output contact OUT107 not used—set equal to zero)
Operation of Output Contacts for Different Output Contact Types
Output Contacts OUT101 Through OUT107
The execution of the serial port command
PULSE
n
(
n
= OUT101 through OUT107) asserts the
corresponding Relay Word bit (OUT101 through OUT107) to logical 1. The assertion of
SEL
OGIC
control equation setting OUT
m
(
m
= 101 through 107) to logical 1 also asserts the
corresponding Relay Word bit OUT
m
(
m
= 101 through 107) to logical 1.
The assertion of Relay Word bit OUT
m
(
m
= 101 through 107) to logical 1 causes the
energization of the corresponding output contact OUT
m
coil. Depending on the contact type (a
or b), the output contact closes or opens as demonstrated in Figure 7.26. An “a” type output
contact is open when the output contact coil is deenergized and closed when the output contact
coil is energized. A “b” type output contact is closed when the output contact coil is deenergized
and open when the output contact coil is energized.
Notice in Figure 7.26 that all four possible combinations of output contact coil states (energized
or deenergized) and output contact types (a or b) are demonstrated. See
Output Contact
Jumpers
in
Section 2: Installation
for output contact type options.
Output contact pickup/dropout time is typically 4 ms.
ALARM Output Contact
Relay Self-Tests
in
Section 13: Testing and Troubleshooting
.
When the relay is operational, the ALARM output contact coil is energized. The alarm
logic/circuitry keeps the ALARM output contact coil energized. Depending on the ALARM
output contact type (a or b), the ALARM output contact closes or opens as demonstrated in
Figure 7.26. An “a” type output contact is open when the output contact coil is deenergized and
closed when the output contact coil is energized. A “b” type output contact is closed when the
output contact coil is deenergized and open when the output contact coil is energized.
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......