2-6
Installation
Date Code 20011205
SEL-311A Instruction Manual
Potential Transformer Inputs
Note the signal labels (VA, VB, VC, N) on terminals Z09 through Z12. Figure 1.2 shows the
internal connection for terminals VA, VB, and VC. Terminals VS and NS are not used in the
SEL-311A, although internal components are in place for future upgrades.
Wye-Connected Voltages
Any of the single-phase voltage inputs (i.e., VA-N, VB-N, or VC-N) can be connected to
voltages up to 150 V continuous. Figure 2.5 shows an example of wye-connected voltages.
System frequency is determined from the voltages connected to terminals VA-N.
Serial Ports
All ports are independent—you can communicate to any combination simultaneously.
Serial Port 1 on all the SEL-311A Relay models is an EIA-485 port (4-wire). The Serial Port 1
plug-in connector accepts wire size AWG 24 to 12. Strip the wires 0.31 inches (8 mm) and
install with a small slotted-tip screwdriver. The Serial Port 1 connector has extra positions for
IRIG-B time-code signal input (see Table 10.2; also see following discussion on IRIG-B time
code input).
All EIA-232 ports accept 9-pin D-subminiature male connectors. Port 2 on the SEL-311A Relay
includes the IRIG-B time-code signal input (see Table 10.1; also see following discussion on
IRIG-B time-code input).
The pin definitions for all the ports are given on the relay rear panel and are detailed in
Table 10.1 through Table 10.3 in
Section 10: Serial Port Communications and Commands
.
Refer to Table 2.1 for a list of cables available from SEL for various communication
applications. Refer to
Section 10: Serial Port Communications and Commands
for detailed
cable diagrams for selected cables (cable diagrams precede Table 10.3).
Note
: Devices not manufactured by SEL are listed in Table 2.1 for the convenience of our
customers. SEL does not specifically endorse or recommend such products, nor does
SEL guarantee proper operation of those products, or the correctness of connections,
over which SEL has no control.
For example, to connect any EIA-232 port to the 9-pin male connector on a laptop computer,
order cable number C234A and specify the length needed (standard length is eight feet). To
connect the SEL-311A Relay Port 2 to the SEL-2020 Communications Processor that supplies
the communication link and the IRIG-B time synchronization signal, order cable number C273A.
For connecting devices at distances over 30 feet, SEL offers fiber-optic transceivers. The
SEL-2800 family of transceivers provides fiber-optic links between devices for electrical
isolation and long-distance signal transmission. Contact SEL for further information on these
products.
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......