For this example, the first reclose attempt at Breaker 3 is 40 cycles after the TRIP condition
is gone.
Because 79RS limits the duration of CLOSE output operation, the reset time (79RS) must be
at least as long as it takes the breaker to completely close. The 79RS timer also serves to
block automatic reclosing for 79RS time period after an operator (or SCADA) closes the line
breaker. This feature allows the local operator to retain control of the line breaker. For this
example, the 79RS timer is set for 240 cycles or four seconds.
For the relay at Breaker 3:
- Setting Limit Check
7901 timer has a primary limit check of 0 to 8,000 cycles. The 79RS timer has a primary
limit check of 60 to 8,000 cycles. There is no secondary limit check for 79OI or 79RS. For
this example, each open interval and 79RS reset timer setting lies within the relay setting
limits.
- Other Settings Affected
Please note that the 52BT timer should be set less than the open interval timer if you need the
switch-onto-fault logic enabled for the line test shot (see 52BT Setting for details).
Close Supervision Settings (PSVC, 27VLO, 59VHI, 25DV, SYNCP, 25T, VCT)
The SEL-221F relay includes two functions which can supervise close operations, including
reclosures and external close operations.
The voltage condition checking function supervises closures based upon hot-bus/dead-line,
hot-line/dead-bus, or either condition. The synch-check function determines whether an
energized line and energized bus are in synchronism. The voltage condition checking
function uses the PSVC, 27VLO, 59VHI, SYNCP, and VCT settings. The synch-check
function uses the 59VHI, 25DV, SYNCP, and 25T settings. The polarizing inputs are VA,
VB, and VC. The relay uses sync voltage input, VS, in the voltage checking and sync
checking logic.
Voltage Checking Function
Enable the voltage checking function by selecting a PSVC setting of S, P, or E. Voltage
checking is disabled when you select PSVC = N. When PSVC = S, the relay asserts Relay
Word bit VSC when VS > 59VHI and VP1 < 27VLO (live sync/dead polarizing) for VCT
time. When PSVC = P, the relay asserts Relay Word bit VSC when VP1 > 59VHI and VS
5 - 8
Applications
SEL-221F, -1 Instruction Manual
Date Code 920508
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...