MAINTENANCE & TESTING
TEST PROCEDURES
Test Aids Provided by the Relay
The following features assist you during relay testing and calibration.
METER
Command
The METER command shows the voltages and currents presented to the
relay in primary values. The relay calculates Megawatts (MW) and
Megavars (MVAR) from these voltages and currents. These quantities are
useful for comparing relay calibration against other meters of known
accuracy.
When testing the relay, first verify relay calibration against meters of
known accuracy. Each relay is calibrated at the factory prior to shipment
and should not require further adjustments. If calibration is necessary,
refer to the Calibration portion of this section. Consider all tests invalid if
you determine that the relay is out of calibration.
The relay allows you to reassign front panel targets to indicate elements
and intermediate logic results in the Relay Word as well as input and
output contact status. Use the TARGET command to reassign the front
panel LEDs. Once target LEDs are reassigned from the default targets,
the front panel targets are no longer latching. This means the targets
follow the pickup and dropout condition in much the same manner as an
output contact. See Section 3: COMMUNICATIONS for more infor-
mation about the TARGET command.
By using the target LEDs for testing, you need not change the relay
settings during testing.
The relay generates an eleven cycle event report in response to faults or
disturbances. Each event report contains voltage and current information,
relay element states, and input/output contact information in quarter-cycle
resolution. If you question the relay response or your test method, use the
event report for more information.
Each event report is date and time tagged relative to the sixteenth quarter-
cycle. Each report is triggered upon assertion of designated relay
elements and/or contact inputs and outputs. If the timeout of a protective
element results in TRIP output contact closure, the trip generates a second
event report. Thus, the relay generates two event reports: the first when
TARGET
Command
Event
Reporting
Date Code 920508
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-1
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...