- Setting Limit Check
The primary limit check allows LOPE settings of N, Y, 1, 2, 3, or 4.
- Relay Word Bits and Other Settings Affected
If LOPE = N or 4, the mho distance elements are not blocked from operating during an LOP
condition.
Serial Port(s) Timeout Settings (TIME1, TIME2)
The TIME1 and TIME2 settings allow their respective ports to time out after the relay detects
a period of inactivity for that port. After timing out, access for the port returns to Level 0
and no automatic messages are transmitted to it. In this example, a modem is connected to
PORT 1. This requires a definite-time setting for the port to prevent accumulation of toll
charges if an operator does not hang up. PORT 2 is to be connected to an SEL-DTA and
should never time out. This allows the SEL-DTA to receive any automatic message trans-
mitted by the relay.
- Setting Limit Check
The TIME1 and TIME2 limit check allows settings of 0 - 30 minutes. A zero setting signifies
that the port never times out. There is no secondary limit check for this setting.
- Other Settings Affected
None.
Autoport Designation Setting (AUTO)
The AUTO setting specifies the port to which the relay directs automatically generated
messages. The example has a modem connected to PORT 1 and an SEL-DTA connected to
PORT 2. Since only the SEL-DTA is required to receive automatic messages, the AUTO
setting is 2.
Date Code 920508
Applications
SEL-221F, -1 Instruction Manual
5-29
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...