Quarter
Cycle
Event Report Shows:
33-39
Fault detecting elements remain asserted
5 in 52A column changes to a period indicating deassertion of the 52A input.
40
G in 50P column indicates that phase current has dropped below the 50P setting
in all three phases, but is still above the 50NG setting.
41-44
Postfault conditions:
Period in 21G column indicates that the ground distance elements have dropped
out.
3 in A3 column drops out, indicating that all reclose initiating elements have
deasserted.
Voltage and current samples go to zero, indicating that the breaker is open and
line deenergized. Potentials in this example are drawn from line-side PTs.
P in the 27P column indicates that the undervoltage elements associated with the
polarizing voltage input is picked up.
No protective relay elements are picked up.
T in TP Outputs column shows that trip is still asserted. The 9.0 cycle TDUR
setting ensures that the trip contacts remain closed for at least nine cycles.
The event summary shows that the fault was an A-G fault in Zone 1, at approximately 75
miles from the relay location. The fault duration was 6.25 cycles and maximum phase
current magnitude at the midpoint of the fault was 647.5 amps primary.
FIRMWARE IDENTIFICATION
The relay provides a Firmware Identification Data (FID) string to identify the relay software
version installed. The FID string is included near the top of each full length event report.
The string format is as follows:
FID =
[PN] - R[RN] - V[VS]- D[RD] - E[ER],
Where:
[PN] =
Product Name
[RN] =
Revision Number
[VS] =
Version Specifications
[RD] =
Release Date
[ER] =
Version Specifications: EEROM
Date Code 920423
Event Reporting
SEL-221F, -1 Instruction Manual
4-15
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...