Zone 2 and 3 Distance Element Timers
Zone 2 ground distance element timer (Z2DG) range: 3 - 2000 cycles in quarter-cycle steps
Zone 2 phase distance element timer (Z2DP) range: 3 - 2000 cycles in quarter-cycle steps
Zone 3 timer (Z3DP) range: 3 - 2000 cycles in quarter-cycle steps
Note:
The instantaneous and time delayed outputs of the Zone 3 distance elements are
separate in the Relay Word, permitting access to both. This allows use of a time
delay for time-stepped backup functions while maintaining the required instantaneous
outputs for communication-based protection schemes.
Overcurrent Elements
Nondirectional Phase Overcurrent Elements
(Secondary Quantities)
50AG, 50BG, 50CG (low-set ground fault detectors)
Pickup: 0.5A to 25 times 51NP, but less than 40 A, ±0.1 A ±2% of setting
Transient overreach: ±5% of set pickup
50AP, 50BP, 50CP (phase fault detectors)
Pickup: 0.5 to 40 A, ±0.1 A ±2% of setting
Transient overreach: ±5% of set pickup
50AH, 50BH, 50CH (high-set phase overcurrent elements)
Pickup: 0.5 to 80 A, ±0.1 A ±2% of setting
Transient overreach: ±5% of set pickup
Ground Overcurrent Elements
(Secondary Quantities)
50N residual overcurrent element
Nondirectional element supervises ground distance elements
Pickup: 0.5 A to 25 times 51N pickup, but less than 40 A
Transient overreach: ±5% of set pickup
51N residual time-overcurrent element
Selectable curve shape
(four curve families)
- Moderately Inverse
(curve family 1)
- Inverse
(curve family 2)
- Very Inverse
(curve family 3)
- Extremely Inverse
(curve family 4)
Time dial: 0.50 to 15.00 in 0.01 steps
Pickup: 0.5 to 8.0 A, ±0.05 A ±3% of setting
Timing: ±4% and ±1 cycle for residual current magnitude between 2 and 20
multiples of pickup
May be directionally controlled (51NTC setting)
Date Code 920508
Specifications
SEL-221F, -1 Instruction Manual
2-9
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...