Voltages VAB, VBC, and VCA should read less than 1.5 kV.
Similarly, currents IA, IB, and IC should equal the applied current times
the current transformer ratio. With the Example 230 kV Line settings, you
should obtain:
I A = I B = I C = ( 5 A ) ( 2 0 0 )
1000 A (±1%).
Difference currents IAB, IBC, and ICA should be less than 20 amperes.
The power reading, P (MW), should read:
(VA)(IA) + (VB)(IB) + (VC)(IC) = 300 MW.
The reactive power reading Q (MVAR) should be less than 5 MVAR.
MHO ELEMENT TESTING
Before you begin testing the mho distance elements, determine the test quantities. Refer to
the end of this section for a simple program (ONEBUS) to calculate voltages and currents
required to simulate a power system fault at the line angle.
Note:
ONEBUS is not required to test the relay, it is included in the manual as a test aid.
During mho element tests, we recommend disabling the loss-of-potential (LOP) logic by
setting LOPE = N in the setting procedure. This prevents an LOP condition from blocking
mho distance elements. You must enable the LOP feature during LOP testing.
A. Determining Fault Simulation Values - Phase-Phase and Phase-Ground Faults
All line impedance entries for the ONEBUS program must be entered in secondary values.
Convert the primary impedance settings from your relay setting sheet or SHOWSET printout
to secondary values with the following formula:
R1
secondary
= R1 (
Current Transformer Ratio
)
Potential Transfoermer Ratio
X1 secondary
= X1 (
Current Transformer Ratio
)
Potential Transformeer Ratio
R0
secondary
= R0 (
Current Transformer Ratio
Potential Transformer Ratio
)
X0
secondary
= X0 (
Current Transformer Ratio
)
Potential Transformer Ratio
Date Code 920508
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-15
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...