Output Contact Explanation
The TRIP output closes in response to any of the following:
1.
Any Zone 1 three-phase, phase-phase, or line-to-ground fault
2.
Any Zone 2 three-phase or phase-phase fault which persists for 30 cycles
3.
Any Zone 2 line-to-ground fault which persists for 30 cycles
4.
Any Zone 3 three-phase or phase-phase, or line-to-ground fault which persists for 40
cycles
5.
Any forward line-to-ground fault which results in expiration of the residual time-
overcurrent element (51NT)
6.
IN1 input assertion if IN1 is set in a tripping logic mask
7. OPEN command execution
The A3 output contacts are set to close when reclose initiating fault conditions occur. The A4
output contacts are set to close when reclose cancelling conditions occur.
The programming of output relays A1 - A4 and four trip logic masks is explained in detail in
the LOGIC command description, Section 3: COMMUNICATIONS.
Target LED Explanation
G1: The AG ground fault at 75 miles should illuminate the Zone 1 ground fault target.
G2: The AG ground fault at 85 miles should illuminate the G2 target.
G3: The AG ground fault at 135 miles should illuminate only the G3 target.
ø1: The Zone 1 BC fault at 75 miles should illuminate the ø1 target.
ø2: The Zone 2 BC fault at 85 miles should illuminate only the ø2 target.
ø3: The Zone 3 BC fault at 135 miles should illuminate only the ø3 target.
Note:
The target level must be at Level 0 to display the fault targets. See the TARGET
command description in Section 3: COMMUNICATIONS for more information.
Each fault generates a short event report. To see the full event report for the last fault, type
EVENT 1
and press
<ENTER>.
Each event report provides an eleven-cycle record of the
currents, voltages, relay element states, and all contact input and output states. The twelve
newest reports are saved in volatile memory.
This checkout procedure demonstrates only a few relay features. For a complete understand-
ing of relay capabilities, study Functional Description in Section 2: SPECIFICATIONS, the
command descriptions in Section 3: COMMUNICATIONS, and Section 4: EVENT
REPORTING. For more test procedures, see the Full Functional Test portion of this section.
Date Code 920508
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-11
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...