SWITCH-ONTO-FAULT TESTS
Purpose:
1.
Verify 52BT timer accuracy and MTO (Switch-Onto-Fault) Logic Mask.
2.
Verify that elements enabled to trip via the MTO logic mask are only enabled
when the breaker is open for a duration exceeding the 52BT setting (52BT bit in
Relay Word is asserted).
Method: 1.
Program one of the available output contacts (A1 - A4) to follow the 52BT bit
in the Relay Word.
2.
Use the 52A contact input deassertion (control voltage on to off) to start an
external timer.
3.
Use the 52BT programmed contact output assertion (open to close) to stop the
timer.
4.
Compare the timer value to the 52BT setting.
5.
To make sure the elements in the MTO logic mask are only enabled when
52BT = 1, apply a fault to pick up an element masked into the MTO logic
mask but not the MTU mask.
6.
Table 7.16 contains prefault and fault voltage and current quantities for a
Zone 2 AG fault.
Prefault:
Table 7.16: Zone 2 AG Fault Quantities
VA
VB
VC
IA
IB
IC
67.00
67.00 67.00
0.00
0.00
0.00
Volts/Amps
0.0° -120.0°
120.0°
0.0°
0.0°
0.0°
Degrees
2AG Fault:
VA
VB
VC
IA
IB
IC
35.59
74.39 74.27
3.03
0.00
0.00
Volts/Amps
0.0° -128.6°
128.7°
-80.4°
0.0°
0.0°
Degrees
7.
Apply the Zone 2 AG fault with the breaker closed (52A = 1 and 52BT = 0).
The relay should not trip instantaneously.
7-36
Maintenance & Testing
SEL-221F, -1 Instruction Manual
Date Code 920508
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...