When you finish entering setting changes, it is not necessary to scroll through the remaining
settings. Type
END <ENTER>
after your last change to display the new settings and
enable prompt. Do not use the END statement at the Relay ID setting. Use
<CTRL> X
to
abort the SET procedure from any point.
After you enter all data, the relay displays the new settings and prompts for approval to
enable them. Answer
Y <ENTER>
to approve the new settings. Error messages notify
you when entry combinations result in an out-of-range secondary setting. If all settings are
acceptable, the relay enables them, closes the ALARM contact momentarily, and clears the
event buffer.
A list of relay settings and the primary limit checks follow. Please note that each setting must
also be within the secondary setting limit of the relay.
R1, X1
Pos. seq. primary impedance of line (0-9999 ohms)
R0, X0
Zero seq. "
"
"
" (0-9999 ohms)
LL
Line length (0.1-999 miles)
CTR
CT ratio (e.g., for 600:5, enter 120) (1-6000)
PTR
PT ratio (e.g., 1200:1, enter 1200) (1-10,000)
SPTR
Synchronization voltage transformer ratio (1-10,000)
MTA
Maximum torque angle for mho elements (47° - 90°)
79OI
Reclosing relay open interval (0 to 8,000 cycles; 0 disables reclosing)
79RS
Reclosing relay reset time (60 to 8,000 cycles)
PSVC
Polarizing and Synchronizing voltage checks (N: none, S: LSDP, P: LPDS, or
E: either)
27VLO
Dead voltage threshold (0-2000 kV)
59VHI
Live voltage threshold (0-2000 kV)
25DV
Difference voltage threshold (0-2000 kV)
SYNCP
Do you want to synch-check to phase A, B, or C?
25T
Synch-check timer (0-8000 cyc)
VCT
Voltage condition timer (0-8000 cyc)
A1TP
A1 contact output pickup delay (0-8000 cyc)
A1TD
A1 contact output dropout delay (0-8000 cyc)
Z1%
Zone 1 reach (percent of line length: 0 to 2000%)
Z2%
Zone 2 reach (percent of line length: 0 to 3200%)
Z3%
Zone 3 reach (percent of line length: 0 to 3200%)
Z2DP
Zone 2 delay for phase-to-phase faults (3-2000 cycles in quarter-cycle steps)
Z2DG
Zone 2 delay for ground faults (3-2000 cycles in quarter-cycle steps)
Z3D
Zone 3 delay for both phase-to-phase and ground faults (3-2000 cycles in quarter-
cycle steps)
TDUR
Minimum TRIP output duration (0-2000 cycles in quarter-cycle steps, 0 disables the
OPEN Command)
3-22
Communications
SEL-221F, -1 Instruction Manual
Date Code 961208
Содержание SEL-221F
Страница 3: ......
Страница 8: ...Time Curve C1 Time Curve C2 Time Curve C3 Time Curve C4 Date Code 961202 SEL 221F Relay Addendum 3 ...
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Страница 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Страница 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Страница 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Страница 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Страница 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Страница 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Страница 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Страница 170: ...Figure 6 2 Horizontal Front and Rear Panel Drawings Date Code 920508 Installation 6 7 SEL 221F 1 Instruction Manual ...
Страница 174: ...Figure 6 8 Dc External Connection Diagram Typical Date Code 920508 Installation SEL 221F 1 Instruction Manual 6 11 ...
Страница 228: ...APPENDICES TABLE OF CONTENTS Parts Placement Diagram Date Code 920508 Table of Contents SEL 221F 1 Instruction Manual i ...
Страница 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...