Operating and Menu Concept
EN
· 30.30.01.02851 · 01 · 03/22
35 / 96
5.2.2
Changing the Parameters of the Main menu
If you wish to change values, e.g. the switching points, you have to enter the new value digit by digit.
1.
Use the
button to select the desired parameter.
2.
Confirm using the
button.
The currently set value is displayed and the first digit flashes.
3.
Use the
button to change the value. The value increases by 1 each time the button is pressed. After 9, the
counter goes back to 0 when the
button is pressed.
4.
Press the
button to save the modified value.
The first digit is accepted and the second digit flashes.
5.
Use the
button to select the second digit.
6.
Press the
button to save the modified value.
The second digit is accepted and the third digit flashes.
7.
Use the
button to select the third digit.
8.
Press the
button to save the modified value.
If the value entered lies within the permissible value range, it is accepted and the modified parameter is
displayed.
If the value entered is not within the permitted value range, this is indicated briefly by the display [
]
and the new value is not applied.
If input is interrupted for longer than 1 minute or if no input is made, the display automatically switches to
the measurement display.
5.3
Extended Functions [EF] Menu
An “Extended Functions” menu (EF) is available for applications with special requirements.
5.3.1
Functions in the Extended Functions [EF] Menu
The following table shows an overview of the display codes and parameters in the “Extended Functions”
menu:
Display
code
Parameter
Possible settings
Explanation
Energy-saving
function
Control function off
Control active
Control with leak monitoring active
Deactivate auto.
control shutoff
Suppresses the automatic valve protection function
when set to
.
Cannot be switched on when
.