Operating Manual 90° ACTUSAFE CMF(S)QT
OM-ENGLISH-Failsafe-QT-16xx-V2.00-2022.03.01
20 Technical data
The power-save mode is defined as follows:
• No power supply (the controller is powered exclusively through the 24 V auxiliary voltage input).
• The backlight of the LCD display switches off automatically.
• No additional hardware options included (Profibus Interface, DeviceNet interface, relay board, etc. . . ).
• Binary outputs and the mA output are not enabled; when activating, the respective currents must be added to the
total current consumption.
20.6
Connections
20.6.1
Connections for non explosion-proof version
Power/motor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Industrial plug with 6 pins
Screw connection 16 A,
max. 2.5 mm
2
, AWG14
Control signals: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Industrial plug with 24 pins
Screw connection
16 A, max. 2.5 mm
2
, AWG14
Optionally, contacts are available in crimp or cage clamp designs.
20.6.2
Connections for explosion-proof version
Power/motor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminals with screw connection
16 A, 0.5. . . 4 mm
2
, AWG20. . . AWG12
Control signals: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .terminals with screw connection
4 A, 0.5. . . 2.5 mm
2
, AWG20. . . AWG14
87
Содержание CM03
Страница 1: ...Operating Manual 90 ACTUSAFE CMF S QT OM ENGLISH Failsafe QT 16xx V2 00 2022 03 01 ...
Страница 97: ...CM03 FSQT ...
Страница 98: ...CM06 FSQT ...