7 Commissioning
7.6.1
Setting procedure:
Figure 10:
Cover removing
1. Remove cover according Figure 10, page 15
NOTE:
In the version with handwheel there is a cable connection which has to be unplugged.
2. Loosen, but do not remove 4pcs of screws according Figure 11, page 16.
3. Insert a 3mm allen key into the radial borehole of flange.
4. Turn flange with the help of the allen key in direction according Figure 11, page 16
Half of possible rotating angle will approximately double Failsafe speed of actuator.
While holding flange with key in desired position retighten screws.
5. In the version with handwheel reconnect the cable to the cover
6. Remount the cover while being aware of correct positioning of the O-ring sealing.
7. Retest the actuator to check for correct Failsafe speed.
17