7 Parameter menu
Operating Manual 90° ACTUSAFE CMF(S)QT
OM-ENGLISH-Failsafe-QT-16xx-V2.00-2022.03.01
continued from previous page
Menu item
Sub-menu item
poss. setting
Notes / comments
34: Torque Closed
Masked
As Torque CLOSED, but it will supress (mask) this signal
in the end position upon torque-dependent switch-off.
35:Ready Remote
Ready and Remote operating mode
36: Ready Local
Ready and Local operating mode
37: Ready
Local/remote
Ready and Local or Remote mode
38: Emerg. Open
Locked
Lock OPEN is enabled. OPEN command is internally
queued with the highest priority and will not be dropped
even in the end position.
39: Emerg. Closed
Locked
Lock CLOSED is enabled. CLOSED command is
internally queued with the highest priority and will not be
dropped even in the end position.
40: Failsafe OK1
Failsafe OK (only for Failsafe actuators)
41: Failsafe OK2
Failsafe OK and Ready (only for Failsafe actuators)
42: Failsafe OK3
Failsafe OK,Ready and Remote (only for Failsafe
actuators)
43: Emerg. Locked
Lock Open or Lock Closed is enabled.
44:
Ready/TorqueOK
Actuator is ready and no torque switch-off
45: Ready /
Remote /
TorqueOK
Actuator is ready for operation in REMOTE mode and no
torque switch-off
46: Pos.=Int1
Position = Intermediate position 1. The width of the
interval is set with the parameter P8.6.
47: Pos.=Int2
Position = Intermediate position 2. The width of the
interval is set in parameter P8.6.
48: Pos.=Int3
Position = Intermediate position 3. The width of the
interval is set in parameter P8.6.
49: Pos.=Int4
Position = Intermediate position 4. The width of the
interval is set in parameter P8.6.
50:
Pos.=EmergPos
Position = emergency position. The width of the interval
is set in parameter P8.6.
51: Bus Bit 1
In existing bus interface (hardware option), the output is
set according to the selected bit bus.
52: Bus Bit 2
53: Bus Bit 3
54: Bus Bit 4
55: Bus Bit 5
56: Bus Bit 6
57: Bus Bit 7
58: Bus Bit 8
59: Virtual 1
Configurable output function
60: Virtual 2
61: Virtual 3
62: Virtual 4
63: Control OK
The SMARTCON control is operational.
64: Control voltage
OK
The auxiliary voltage for the SMARTCON control is OK.
This function is only available if the auxiliary voltage
output is not switched on (P6.5 to 0).
65: PVST OK
The PVST was successful.
66: PVST Failure
The PVST was not successful.
67: PVST Active
A PVST was triggered. The actuator is running a PVST.
68: Emerg. OPEN
Emergency OPEN command is active. The signal
remains active, as long as the emergency command is
active, even if the end limit is reached.
69: Emerg.
CLOSE
Emergency CLOSE command is active. The signal
remains active, as long as the emergency command is
active, even if the end limit is reached.
continued on next page
54