19
All settings of the dip switches must be performed prior to the commissioning and before power is supplied to the
controller, in order to ensure a proper functionality of the settings.
SW1:
1. Slow: Optional soft-start and soft-stop setting
ON: The motors move at a continuous speed during the opening and closing up to the end positions.
OFF: The motors reduce their speed during the closing and opening before they reach the end positions (protects the gearbox).
2.-3. O Over_C2: Optional force setting
The factory-set forces (value 1) are designed to enable a smooth operation of standard gates (which are intended for use
with this drive). The forces exerted in the factory default setting should fundamentally be sufficient to fully open and close
the gate to be operated. In the factory default setting, the drive complies with the legal or relevant standards (for example,
EN 12455, EN 12453; EN 60335-2-95) pertaining to the requirements for the operating forces and therefore the maximum
permissible force limits. The forces to be exerted by the drive can be increased if required, through the procedure described
below (values 2-4).
NOTE
This could be required, for example, if the „gate open“ or “gate closed“ end stops are not reached with the factory default
setting (value 1). In this case, the setting for the maximum force must be increased gradually, until the respective end stop is
reached.
Winter operation:
We recommend increasing the force level during the winter months if the „door open“ or „door closed“ end stop is not rea
-
ched with the factory default setting (value 1). In this case, the setting for the maximum force must be increased gradually,
until the respective end stop is reached.
CAUTION
An increased setting which deviates the factory default setting (value 1) can lead to serious personal injury and even a mor-
tal danger, as well as severe property damage!
An increased force value which deviates from the factory default setting (value 1) increases the forces exerted onto the gate
during the opening and closing motion. If a factory default setting is changed, there is a danger of serious personal injury up
to mortal danger through a possible jamming or crushing of persons or items within in the gate area, as well as the risk of
damage to property, since a force setting which deviates from the factory default setting can possibly lead to an exceeding of
the specified maximum permissible force limits. Therefore, the following shall apply:
After each force setting change (values 2-4) which deviates from the factory default setting (value 1), the full compliance
with the statutory or relevant standards regarding the force limit values must be checked, approved and documented by a
competent person, in order to exclude the indicated dangers for life and limb.
More information is available on page 299
4.-6. Auto_C1 - Auto_C3: Optional automatic closing function
The door closes independently after the pre-set time, once the end position „open“ has been approached. For your own
safety, the automatic closing function may only be enabled, if the system is operated in conjunction with an additional safety
device, e.g. a light barrier.
More information is available on page 300
7. P_Mode: Optional customization of the pedestrian function
ON: Press the button B on the hand-held wireless remote control to only open one door leaf (45° opening angle).
OFF: Pedestrian function is disabled. The drive opens and closes completely.
8. Light: Optional signal lamp setting
A 24 V signal lamp can be connected optionally.
ON: The signal lamp will flash for 3 seconds before the gate is set in motion again, and during the complete opening and
closing cycle
OFF: The signal lamp will flash during the opening and closing cycle
A LEGEND AND EXPLANATION OF THE SWITCHES FOR THE PROGRAMMING
Содержание TWIN 300
Страница 1: ...TWIN 300...
Страница 2: ......
Страница 132: ...132 Schellenberg Schellenberg Schellenberg Tor geschlossen 136...
Страница 141: ...141 Schellenberg Schellenberg Schellenberg 145...
Страница 159: ...159 Schellenberg Schellenberg Schellenberg...
Страница 168: ...168 Schellenberg 172...
Страница 258: ...258...
Страница 262: ...262 SW1 1 2 3 _C1 _C2 1 EN 12455 EN 12453 EN 60335 2 95 2 4 1 1 1 1 2 4 299 4 6 Auto_C1 Auto_C3 300 7 P_ 45 8 24 V 3 A...
Страница 274: ...1x 1x 1x 274...
Страница 275: ...4x 2x Art No 60852 60853 2x 4x 1x 3x 2x2 1x 2x 1x2m 1 2 1x7m 275...
Страница 277: ...7m 2m 277...
Страница 278: ...Min 150mm Max 116mm Min 70mm 278...
Страница 281: ...Min 70mm 281...
Страница 282: ...2x B 282 1...
Страница 283: ...283 3 2...
Страница 284: ...284 4...
Страница 285: ...285 5...
Страница 286: ...286 6...
Страница 287: ...287 7...
Страница 288: ...288 8...
Страница 289: ...289 9...
Страница 290: ...290 10...
Страница 291: ...2x 291 11...
Страница 292: ...292 12 13...
Страница 293: ...276 294 294 293...
Страница 294: ...4x 3x 294 14 16 17 15...
Страница 295: ...LED1 LED5 LED2 LED3 LED4 3x 295 18...
Страница 296: ...1 2 3x 2x 296 19...
Страница 297: ...L L Lo Lo 12V G F01 F02 F0 G D S G Mo1 Mo1 Mo2 Mo2 LED5 297 20...
Страница 302: ...LED1 LED5 LED2 LED3 LED4 12V G F01 F02 F0 G D S G LED5 C 4 302...
Страница 303: ...1 2 2 sec 1x 3x SYS learn SYS learn SYS learn RF learn RF learn RF learn LED5 LED5 LED5 10 sec 303...
Страница 304: ...LED1 LED5 LED2 LED3 LED4 12V G F01 F02 F0 G D S G A LED5 C 5 304...
Страница 305: ...307 306 305...
Страница 310: ...LED1 LED5 LED2 LED3 LED4 12V G F01 F02 F0 G D S G C 8 310...
Страница 311: ...10sec LED5 1 10 sec 311...
Страница 312: ...D 312...
Страница 314: ...Mo1 Mo1 Mo2 Mo2 L L Lo Lo 12V G F01 F02 F0 G D S G Art No 60999 60997 LED5 G SW1 SW2 SW3 E 314...
Страница 315: ...Mo1 Mo1 Mo2 Mo2 L L Lo Lo 12V G F01 F02 F0 G D S G 24 V Art No 60020 60021 LED5 SW1 SW2 SW3 315...