135
If no signal is assigned on the EI input terminals, it is always regarded as turning OFF.
Therefore, P1.78 (vibration suppressing anti resonance frequency 0) is always enabled.
To disable the anti resonance frequency, set the anti resonance frequency at 300.0 Hz.
Because in-cycle switching of the anti resonance frequency causes a shock, switch during stoppage without
fail.
In addition, it is recommended to use P1.52 (low-pass filter (for S-curve) time constant) in parallel.
·AD0:(Reference value 60)
·AD1:(Reference value 61)
·AD2:(Reference value 62)
·AD3:(Reference value 63)
Enter the address of positioning data to be followed, among AD0 to AD3.
Refer to the table below when entering.
Address
NO.
AD3
AD2
AD1
AD0
Sequential start
selection:P2.41
Operation mode
In case of internal positioning data
selection:P2.40 = 1(enable)
0
OFF
OFF
OFF
OFF
0: Disable
Address error
1: Enable
Sequential start
2: Homing
Homing operation
3: Immediate value
data operation
Immediate value data operation
1
OFF
OFF
OFF
ON
-
Operation with positioning data 1
2
OFF
OFF
ON
OFF -
Operation with positioning data 2
3
OFF
OFF
ON
ON
-
Operation with positioning data 3
4
OFF
ON
OFF
OFF -
Operation with positioning data 4
5
OFF
ON
OFF
ON
-
Operation with positioning data 5
6
OFF
ON
ON
OFF -
Operation with positioning data 6
7
OFF
ON
ON
ON
-
Operation with positioning data 7
8
ON
OFF
OFF
OFF -
Operation with positioning data 8
9
ON
OFF
OFF
ON
-
Operation with positioning data 9
10
ON
OFF
ON
OFF -
Operation with positioning data 10
11
ON
OFF
ON
ON
-
Operation with positioning data 11
12
ON
ON
OFF
OFF -
Operation with positioning data 12
13
ON
ON
OFF
ON
-
Operation with positioning data 13
14
ON
ON
ON
OFF -
Operation with positioning data 14
15
ON
ON
ON
ON
-
Operation with positioning data 15
·Pulse speed command: (setting value 70)
In speed control mode, the speed is controlled by the pulse command frequency.
When the current multi-speed selection [X1], [X2] and [X3] are all OFF, the signal is ON, the speed is
controlled by the pulse command frequency, the signal is OFF, and the speed is controlled by the speed
command voltage (VREF).
Speed command value (rpm) = input pulse command frequency * 60 * Electronic gear numerator / electronic
gear denominator / encoder single-turn resolution.