26 ACU-280 

SATEL 

Active mode 

Press any key to define whether the detector is to be always active (  – no,   – yes). 

Settings 

To configure parameters and options, use the arrow keys and the number keys. For 
description of the settings, see the section on configuring devices from the DLOADX 
program. 

Filter 

Using the number keys, enter a number from a range of 0 to 50 to define the rules of device 
presence control. 

VERSA / VERSA Plus / VERSA IP 

You can configure the device settings: 

  immediately after registering the device to the controller, 

  using the “Config.device” function (service mode 

“2.Hardware” 

“1.Kpds. & exps” 

“3.Wireless dev.” 

“2.Config.device”). Having started the function, use the 

 and 

 

keys to select the zone to which the device is assigned and press  . 

The programming is performed using the “step by step” method. Described below is how to 
configure the devices for which additional settings are available. 

AGD-100 (AGD-200) 

1.  Enter a number from the 0 to 50 range to define the rules of device presence control. 
2. Press  . 
3.  Define whether the detector is to be always active by pressing any number key (  – no, 

 – yes). 

4. Press  . 
5.  Enter a digit from the 1 to 3 range to define sensitivity (1 – low, 2 – medium, 3 – high). 
6. Press  . 

AMD-100 (AMD-200) / AMD-101 (AMD-201) 

1.  Enter a number from the 0 to 50 range to define the rules of device presence control. 
2. Press  . 
3.  Define whether the detector is to be always active by pressing any number key (  – no, 

 – yes). 

4. Press  . 
5.  When the reed switch settings are displayed, press   (these settings are irrelevant). 

AMD-102 (AMD-202) 

For the magnetic contact: 
1.  Enter a number from the 0 to 50 range to define the rules of device presence control. 
2. Press  . 
3.  Define whether the detector is to be always active by pressing any number key (  – no, 

 – yes). 

4. Press  . 
5.  When the reed switch settings are displayed, press   (these settings are irrelevant). 
For the roller shutter input: 
1.  Enter a digit from the 1 to 8 range to define the number of pulses that will trigger alarm. 
2. Press  . 

Содержание ABAX 2 ACU-280

Страница 1: ...ACU 280 ABAX 2 wireless system controller Firmware version 6 00 acu 280_en 03 19 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Страница 2: ...of the device is located on the enclosure base SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current informa...

Страница 3: ...11 6 1 1 1 Adding new wireless devices 13 6 1 1 2 Removing wireless devices 15 6 1 2 Expander of wireless devices for the VERSA VERSA Plus VERSA IP control panel 16 6 1 2 1 Adding new wireless devices...

Страница 4: ...nal menu 36 9 2 Establishing connection between the program and the controller 36 9 3 Status 37 9 3 1 Comm history 39 9 4 Keyfob state 40 10 Controller firmware update 41 10 1 Updating the firmware of...

Страница 5: ...dio and consequently do not require removal of their enclosure 2 Features Support for up to 48 ABAX 2 wireless devices the number of supported devices depends on the configuration Support for ABAX 2 w...

Страница 6: ...ontrol panel ON no communication with the control panel flashing communication with the control panel OK tamper switch RS 232 port TTL standard 3 1 Terminals 12V power input COM common ground CKM keyp...

Страница 7: ...F ON Table 1 3 2 2 Address setting expander of wireless devices for the INTEGRA INTEGRA Plus control panel Fig 3 DIP switches for setting address when the controller is connected to the INTEGRA INTEGR...

Страница 8: ...ed by people moving around the premises Installing the device in close vicinity of electrical systems is not recommended since it can adversely affect the range of radio signal Several ABAX 2 ABAX wir...

Страница 9: ...SATEL ACU 280 7 Fig 4 Opening the enclosure Fig 5 Installation of enclosure base...

Страница 10: ...ng the DIP switches see DIP switches p 5 1 Define the controller operating mode switches 9 and 10 2 Set the controller s address if the controller is to be connected to the INTEGRA INTEGRA Plus contro...

Страница 11: ...the cover 3 Turn the power on The LED indicator should come on 4 Run the identification function in the control panel see the control panel installer manual The controller will be identified as ACU 1...

Страница 12: ...erating the INTEGRA INTEGRA Plus control panel VERSA KWRL2 wireless keypad for operating the VERSA VERSA Plus VERSA IP control panel 5 3 Keyfob APT 200 bidirectional keyfob Keyfobs are discussed in a...

Страница 13: ...system zones outputs with registered keypads during identification procedure the keypads will be added to the system However if their addresses coincide with those of other devices installed in the s...

Страница 14: ...evices No device No device 1 APD 200 detector 17 APD 200 detector 17 unused unavailable 2 APD 200 detector 18 APD 200 detector 18 unused unavailable 3 AMD 200 detector 19 AMD 200 detector 19 unused un...

Страница 15: ...a wireless device in the Structure window Hardware tab after clicking on the name of the controller on the device list and then on the Zones Outputs tab The device being added is assigned to zones and...

Страница 16: ...anders Settings controller name New device When adding a device you can select the alarm system zone to which you want to assign the device It can be one of the unoccupied zones from the pool reserved...

Страница 17: ...ss devices will be read from the controller these data are not read after clicking on the button in the main menu 2 Click on the device you want to remove if the device occupies two or more positions...

Страница 18: ...tional zones will be assigned to the device automatically these will be zones immediately following the selected one If the device is to be also assigned to an output the output number will be the sam...

Страница 19: ...appens you might have entered a wrong serial number press to quit the function 6 Depending on the device if the device takes up only 1 zone or you cannot select how many positions the device is to occ...

Страница 20: ...em settings you can use the DLOADX program or LCD keypad for more information on DLOADX program and LCD keypads refer to the control panel manuals For the INTEGRA INTEGRA Plus control panel DLOADX pro...

Страница 21: ...s and the controller sends commands to the devices switches the detectors into active passive mode starts ends test mode changes configuration of the devices etc The communication period has effect on...

Страница 22: ...ontroller connected to VERSA VERSA Plus VERSA IP control panel 7 2 Functions Test mode to carry out diagnostics service work you can start the test mode in the ABAX 2 system When the system is running...

Страница 23: ...e programmed if the device takes up more than one zone ADD 200 wireless outdoor dusk and temperature detector You can configure sensitivity of the dusk sensor detection threshold first zone temperatur...

Страница 24: ...alarm will be triggered temperature tolerance AVD 100 AVD 200 wireless shock detector and magnetic contact do not configure the magnetic contact settings first zone the AVD 200 detector does not have...

Страница 25: ...communicate to the controller via the repeater the repeater takes up two positions on the list of devices enter the number of the first of them Configuration In the Configuration column you can confi...

Страница 26: ...sor or 2 alarm after motion is detected by microwave sensor ARD 100 ARD 200 Enter a number from the 1 to 16 range to determine sensitivity 1 minimum 16 maximum ASD 150 ASD 250 Enter 2 digits 1st digit...

Страница 27: ...requency from 2000 Hz to 1450 Hz within 1 second Table 6 Types of acoustic signaling available in the ASP 215 siren ASW 100 ASW 200 Enter 0 only remote control 1 remote or manual control or 2 remote o...

Страница 28: ...ngs are available AGD 100 AGD 200 1 Enter a number from the 0 to 50 range to define the rules of device presence control 2 Press 3 Define whether the detector is to be always active by pressing any nu...

Страница 29: ...be always active by pressing any number key no yes 4 Press 5 Enter a digit from the 1 do 4 range to define sensitivity of the PIR sensor 1 minimum 4 maximum 6 Press 7 Enter a digit from the 1 do 8 ran...

Страница 30: ...er a number from the 0 to 50 range to define the rules of device presence control 2 Press 3 Define whether the detector is to be always active by pressing any number key no yes 4 Press 5 Enter a numbe...

Страница 31: ...to define the rules of device presence control 2 Press 3 Use the and keys to define how the acoustic signaling will work disabled 1 2 or 3 type of acoustic signaling see table 6 4 Press 5 Use the and...

Страница 32: ...a high capacity battery the siren can receive transmissions from the controller at any time Therefore the commands to start stop signaling are sent to the siren immediately ASP 215 both outputs can co...

Страница 33: ...assigned is activated in the event of 230 V AC mains loss select the appropriate zone type The second zone to which the radio signal repeater is assigned is activated in the event of battery trouble...

Страница 34: ...for a few seconds by the keyfob LEDs Thus you can get confirmation that the function has been executed or information on the current system status The outputs whose state is presented on the keyfob L...

Страница 35: ...f buttons 1 Click on the field corresponding to the button combination of buttons 2 Enter the zone number and press ENTER 3 Using the SPACE key enable disable the event generating function If the symb...

Страница 36: ...f the Rem ABAX kfbs function available in the service mode in the keypad 2 Hardware 1 Kpds exps 8 Rem ABAX kfbs 8 2 1 Keyfob management using the DLOADX program You can add and delete keyfobs in the V...

Страница 37: ...Right click on the field corresponding to the LED 2 The list of information that can be presented by the LED will be displayed 3 Click on the information items to be presented Removing a keyfob 1 Clic...

Страница 38: ...ta to file Configuration click to open the Connection window About click to display information about the program Connection window Fig 15 ABAX 2 Soft program Connection window Port RS 232 computer CO...

Страница 39: ...cases Power supply Information about current voltage of the controller power supply DIP switches Graphic information about setting of DIP switches Devices status Name blank field Type device type If...

Страница 40: ...sentation Pow volt value of the supply voltage Temperature temperature registered by the temperature sensor in the device Work time work time of the device The time is counted from the moment of the d...

Страница 41: ...m operation This may result in a periodic loss of communication as well as quicker draining of the battery in wireless devices Fig 17 ABAX 2 Soft program Graphs window 9 3 1 Comm history Fig 18 ABAX 2...

Страница 42: ...light green level of the radio signal received from the device by the controller blue level of the interfering signal Buttons click to clear the history of communication of the selected device with th...

Страница 43: ...e 1 Download the ACU 280 controller firmware update program from www satel eu 2 Connect the RS 232 TTL port of the controller to the USB port of the computer To make the connection use the USB RS conv...

Страница 44: ...wer on the controller The LED indicating the status of communication with the control panel will start blinking 5 When the factory default settings are restored the LED will go off for a while and the...

Отзывы: