SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
72/
150
3.10.
Additional C
omponents for the “Energy Counter” Application
The energy counter application (ADE) complies with the standards IEC 60687, IEC 61036, IEC 61268,
IEC 62053-21, IEC 62053-22 and IEC 62053-23.
ES847 option board allows measuring the amount of regenerated energy through the ADE integrated circuit.
The following variables can be measured:
Instantaneous power;
Energy;
Current in each phase;
Voltage in each phase.
How to install ES847 board is detailed in the Motor Drives Accessories Guide.
In addition to ES847 option board, three AC CTs
– one per phase – shall be connected, along with ES917
board for the measurement of the voltage values in each phase (see ES917 Board). The diagram below
shows the wiring required for the correct detection of the regenerated energy.
Figure 12: Wiring diagram for the Energy Counter application
NOTE
Before using the Energy Counter application, measures shall be adjusted
using the dedicated parameters (see the ADE Registers Settings Menu).
Measurement devices (such as a power meter, a current meter and a
voltmeter) are required to check if the values measured through ES847 board
are correct (see Menu n.2
P000919-B
M1
M2