N.
Name
Description
I/O Features
DIP-switch/Notes
27
XAIN8/T1+
“Slow” configurable auxiliary analog input,
number 8
Vfs = 10V, Rin = 30k
SW1.3 = ON
SW1.1-2-4 = OFF
Vfs = 100mV, Rin = 1M
SW1.4 = ON
SW1.1-2-3 = OFF
Ifs = 20mA, Rin = 124,5
SW1.2 = ON
SW1.1-3-4 = OFF
Thermistor temperature measure, number 1
Temperature measure with
PT100.
Compliant with IEC 60751 or
DIN 43735.
SW1.1-4 = ON
SW1.2-3 = OFF
(default)
28
CMA/T1
–
0V for analog inputs for XAIN8 return
Control board zero Volt
29
XAIN9/T2+
“Slow” configurable auxiliary analog input,
number 9
Vfs = 10V, Rin = 30k
SW1.7 = ON
SW1.5-6-8 = OFF
Vfs = 100mV, Rin = 1M
SW1.8 = ON
SW1.5-6-7 = OFF
Ifs = 20mA, Rin = 124,5
SW1.6 = ON
SW1.5-7-8 = OFF
Thermistor temperature measure, number 2
Temperature measure with
PT100.
Compliant with IEC 60751 or
DIN 43735.
SW1.5-8 = ON
SW1.6-7 = OFF
(default)
30
CMA/T2
–
0V for analog inputs for XAIN9 return
Control board zero Volt
31
XAIN10/T3+
“Slow” configurable auxiliary analog input,
number 10
Vfs = 10V, Rin = 30k
SW2.3 = ON
SW2.1-2-4 = OFF
Vfs = 100mV, Rin = 1M
SW2.4 = ON
SW2.1-2-3 = OFF
Ifs = 20mA, Rin = 124,5
SW2.2 = ON
SW2.1-3-4 = OFF
Thermistor temperature measure, number 3
Temperature measure with
PT100.
Compliant with IEC 60751 or
DIN 43735.
SW2.1-4 = ON
SW2.2-3 = OFF
(default)
32
CMA/T3
–
0V for analog inputs for XAIN10 return
Control board zero Volt
33
XAIN11/T4+
“Slow” configurable auxiliary analog input,
number 11
Vfs = 10V, Rin = 30k
SW2.7 = ON
SW2.5-6-8 = OFF
Vfs = 100mV, Rin = 1M
SW2.8 = ON
SW2.5-6-7 = OFF
Ifs = 20mA, Rin = 124,5
SW2.6 = ON
SW2.5-7-8 = OFF
Thermistor temperature measure, number 4
Temperature measure with
PT100.
Compliant with IEC 60751 or
DIN 43735.
SW2.5-8 = ON
SW2.6-7 = OFF
(default)
34
CMA/T4
–
0V for analog inputs for XAIN11 return
Control board zero Volt
35
XAIN12
“Slow” auxiliary analog input, 10V f.s., number
12
Fs = 10V; Rin= 30k
n.u.
36
CMA
0V for analog inputs for XAIN12 return
Control board zero Volt
n.u.
37
XAIN13
“Slow” auxiliary analog input, 10V f.s., number
13
Fs = 10V; Rin= 30k
n.u.
38
CMA
0V for analog inputs for XAIN13 return
Control board zero Volt