SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
114/
150
P550 Max. Voltage Trip Threshold
P550
Range
105
122
105
122% of Rated Vmains (
C500
)
Default
120
120% of Rated Vmains (
C500
)
Level
ENGINEERING
Address
670
Function
This parameter is expressed as a percentage of the rated mains voltage
and sets the trip threshold for the mains Max. Voltage fault.
If
P576
>0, the value in this parameter is affected by the regulations
selected and can no longer be changed.
P551 Max. Voltage Release Ratio
P551
Range
900
1000
0.900
1.000
Default
920
0.920
Level
ENGINEERING
Address
671
Function
This parameter sets the ratio between the trip voltage of the Max.
Voltage fault and its reset value.
P552 Max. Voltage Trip Time
P552
Range
20
1000
0.020
1.000 s
Default
150
0.150 s
Level
ENGINEERING
Address
672
Function
This is the time when the max. voltage trip condition is maintained for the
mains Max. Voltage fault.
If
P576
>0, the value in this parameter is affected by the regulations
selected and can no longer be changed.
P553 Max. Voltage Reset Time
P553
Range
20
1000
0.020
1.000 s
Default
100
0.100 s
Level
ENGINEERING
Address
673
Function
This is the time when the max. voltage reset condition is maintained to
deactivate the mains Max. Voltage fault.
P554 Min. Voltage Trip Threshold
P554
Range
60
90
60
90% of Vn
Default
80
80% of Vn
Level
ENGINEERING
Address
674
Function
This parameter is expressed as a percentage of the rated mains voltage
and sets the trip threshold for the mains Min. Voltage fault.
If
P576
>0, the value in this parameter is affected by the regulations
selected and can no longer be changed.