SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
116/
150
P560a Instantaneous Overvoltage Trip Time
P560a
Range
1
1000
0.001
1.000 s
Default
10
0.010 s
Level
ENGINEERING
Address
698
Function
Time span of the Instantaneous Overvoltage fault duration for the
activation of the mains Instantaneous Overvoltage.
If
P576
>0, the value in this parameter is affected by the regulations
selected and can no longer be changed.
P561a Instantaneous Overvoltage Reset Time
P561a
Range
1
1000
0.001
1.000 s
Default
10
0.010 s
Level
ENGINEERING
Address
699
Function
Time span of the Instantaneous Overvoltage fault reset duration for the
deactivation of the mains Instantaneous Overvoltage.
P558 Instantaneous Undervoltage Trip Threshold
P558
Range
50
90
50
90% of Vn
Default
60
60% of Vn
Level
ENGINEERING
Address
678
Function
This parameter is expressed as a percentage of the rated mains voltage
and sets the trip threshold for the mains Instantaneous Undervoltage
fault.
If
P576
>0, the value in this parameter is affected by the regulations
selected and can no longer be changed.
P559 Instantaneous Undervoltage Release Ratio
P559
Range
1000
1100
1.000
1.100
Default
1060
1.060
Level
ENGINEERING
Address
679
Function
This parameter sets the ratio between the trip voltage for the
Instantaneous Undervoltage fault and its reset value.
P560 Instantaneous Undervoltage Trip Time
P560
Range
1
1000
0.001
1.000 s
Default
10
0.010 s
Level
ENGINEERING
Address
680
Function
This is the time when the instantaneous undervoltage trip condition is
maintained for the mains Instantaneous Undervoltage fault.
If
P576
>0, the value in this parameter is affected by the regulations
selected and can no longer be changed.