3.10.3.
ES917 Board
ES917 board measures the mains voltage. It detects the three line voltages and it outputs three voltage
signals proportional to the inputs. These outputs may be proportional to phase to phase voltages (in that
case, they must not be used) or they may be proportional to each voltage phase to neutral (in that case, they
are allocated to the Energy Counter).
CAUTION
Exclusively use the ES917 board fitting the rated voltage of the grid it is to
be connected to (see below).
3.10.4.
ES917 ID
Description
Part Number
ES917 for mains voltage measure, class 2T-4T
ZZ4091706
ES917 for mains voltage measure, class 5T-6T
ZZ4091707
3.10.5.
ES917 Terminals
M1, screwable terminal board suitable for cable cross-sections 0.2÷2.5mm
2
(AWG 24-14)
M2, screwable terminal board suitable for cable cross-sections 0.2÷2.5mm
2
(AWG 24-14)
NOTE
The signals dedicated to the Energy Counter application are marked as
NOTE
The terminals that are not mentioned are intended as n.c. (not connected).
N.
Name
Description
I/O Features
Notes
6
N
Neutral
Three-phase reference
Input
8
T
Phase T with respect to Neutral
460Vac max, Irms<500
μA
Input
10
S
Phase S with respect to Neutral
Input
12
R
Phase R with respect to Neutral
Input
N.
Name
Description
I/O Features
Notes
1
VRN
Phase R to N scaled voltage
836V Input
10V Output for
ZZ4091706
1518V Input
10V Output
for ZZ4091707
Output
2
VRS
Phase R to phase S scaled voltage
n.u.
3
VSN
Phase S to N scaled voltage
Output
4
VST
Phase S to phase T scaled voltage
n.u.
5
VTN
Phase T to N scaled voltage
Output
6
VTR
Phase T to phase R scaled voltage
n.u.
7
N0
Low Voltage signal reference
0V
n.u.
8
N0
Low Voltage signal reference
0V
n.u.
9
N0
Low Voltage signal reference
0V
16
0V EXT
-
-
Not mounted
17
+24V EXT
-
-
Not mounted
18
NO
-
-
Not mounted
19
COM
-
-
Not mounted
20
NC
-
-
Not mounted
21
AL
–
-
-
Not mounted
22
AL+
-
-
Not mounted