5.4.
ADE Registers Settings Menu
5.4.1. Overview
This submenu allows calibrating the measures contained in Menu n.2
– ADE Measures. ES847 option board
and its external components (see Additional C
omponents for the “Energy Counter” Application) are required
(please refer to the
Sinus Penta’s Installation Instructions manual). Measurement devices (such as a power
meter, a current probe and a voltmeter) are required to check if the values measured through ES847 board
are correct.
To activate ES847 board, set parameter
R023
=
5:XMDO+ADE+PT100 or
6:XMDO+ADE+PT100+Pout (see the Expansion Board Configuration Menu).
“ADE” is part of the name of the integrated circuit (ADE7758) installed in ES847 board. This integrated circuit
ensures high-precision three-phase measurement of electric energy, and is capable of detecting active
energy, reactive energy, apparent energy and of calculating RMS values.
This integrated circuit complies with the following standards: IEC 1036, IEC 61036 and following
amendments.
Particularly, standard IEC 61036:1996 covers “Alternating current static watt-hour meters for active energy
(classes 1 and 2)
”.
ADE7758 provides calibration characteristics for each phase, such as offset/gain/phase/power correction.
ADE registers are described below.