2.1 OPERATIONAL ENVIRONMENT
2.2 INSTALLATION MATTERS
Table 2.1 Operational Environmental Requirements
Table 2.2 The output Current Derating Factor in Relation to Altitude
Altitude
1,000 m (3300 ft)or lower
1,000~1,500m
1,500~2,000m
2,000~2,500m
2,500~3,000m
1
0.97
0.95
0.91
0.88
(1) Installing base
Install the inverter on a base made of metal or other non-combustible; do not mount it upside down,
obliquely or horizontally.
Install the inverter on a base made of metal or other non-combustible.
Otherwise,it may cause a fire.
Items
Specifications
-10 to+50
℃
; When inverters (22kW or below) are mounted side-by-side without any
clearance between them, the surrounding temperature should be within the range from
-10 to +40°C (14 to 104°F)
3mm (max. amplitude) within 2 ~ 9 Hz
9.8 m/s2 within 9 ~ 20 Hz
2 m/s2 within 20 ~ 55 Hz
1 m/s2 within 55 ~ 200 Hz
The inverter must not be exposed to dust, direct sunlight, corrosive , gases, flammable
gases, oil mist, lint and small metal filings ,vapor, electromagnetic interference (welding
machines, power machines) , water drops, or vibration (punch).
Keep away from radioactive materials and flammable object.
Install antivibration pads to reduce vibration if vibration cannot be avoided
No condensation below 90%
Ambient
temperat-
ure
Relative
humidity
Altitude
Environ-
ment Atm-
osphere
Atmosp-
heric
pressure
1,000 m or less (Note 1)
86~106kPa
Installation environment has a direct impact on the normal function of and life span of the inverter, so
install S3800C series of inverters in an environment that satisfies the requirements listed in Table 2.1:
(Note 1) If you use the inverter in an altitude above 1000 m (3300 ft), you should apply an output
current derating factor as listed in Table 2.2.
2.HARDWARE DESCRIPTION AND INSTALLATION
Vibration
Output current derating factor
Warning