Table 2.8 Function of Control Terminals
(
continued
)
Items
Maximum
Operating
voltage
ON Value
OFF Value
2V
27V
50mA
0.1mA
◆
◆
Note:
Digital
common
terminals
Pulse
monitor
DFM
function
DFM
DCM
Output pulse signal. Content of the signal can be chosen from the same
function as the AFM through the setting of function parameters 00.35.
* Impedance can be connected: Min 5kΩ
(Up to two analog voltmeter (DC0~10V can be connected, the input
impedance is 10kΩ).
* Pulse working state: about 50% Pulse rate: 25~ 6000p / s (full scale)
• Pulse output waveform • DFM output circuit example
(1) Output various signals set by 01.20 - 01.24 parameters
(2) Switch from "signal output ON" to "signal output OFF" of the opera-
tion mode between the transistor output terminal MO1~MO4 and the
terminal MCM.
Common terminals output by the transistor are relatively insulated to the
terminals DCM, ACM.
Connect a surge-absorbing diode at both ends of the field coil
when connecting control relay.
Use terminal 24V as power supply terminal (DC24V (supply
voltage range: DC22 ~ 27V), maximum 100mA) when turning
the circuit on. Perform short-circuit between the terminals
MCM-DCM.
Common terminals for analog input signals and terminal DFM output are
insulated for ACM, MCM terminals.
Maximum load current when ON
Leakage current when OFF
Transistors
Output 1
Transistors
Output 2
Transistors
Output 3
Transistors
Output 4
Transistor
outputs
common
terminal
MCM
MO1
MO2
MO3
MO4
15.0 ̄
16.5V
0.1V
max.
Meter
DFM
DCM
<Control circuit>
Functions
Categ-
ory
Terminal
symbol
Terminal
name
Pu
ls
e
ou
tp
ut
Tr
an
si
st
or
s
O
ut
pu
t
<Transistor output circuit specifications>