50
Motor constants after Auto-tuning will be saved in corresponding function parameters automatically.
(2) Preparation Mechanical System
Take dismantling for motor gearing
(3) Auto-tuningn procedures for vector control running
①
Set “3”in function parameter 03
.
04 and press key.
②
Enter a run command. (Set key on keypad as forward running. If it takes reverse running,
Change the data of function parameter 00
.
02).
③
Enter a run command, Tuning starts with the motor stopped. (Tuning time: max. 40~75 s.)
④
The motor is accelerated to approximately 50% of the base frequency and then tuning starts. Upon
completion of measurements, the motor decelerates to a stop.(Estimated tuning time: acceleration
time +20~75s + deceleration time)
⑤
After the motor decelerates to a stop, tuning continues with the motor stopped. (Tuning time: max.
20~35s.)
Primary resistance %R1
(03
.
07*)
Leakage reactance %X
(03
.
08*)
Rated Slip (03
.
12*)
% X correction factor 1
(03
.
53, 03
.
54)
No-load current (03
.
06 *)
Primary resistance% R1 (03
.
07 *)
Leakage reactance% X (03
.
08 *)
Rated Slip frequency (03
.
12 *)
Magnetic saturation factors
1 – 5
Magnetic saturation
expansion factors a ~ c (03
.
16 * ~ 03
.
23 *)
% X correction factor 1, 2 (03
.
53 * 03
.
54 *)
Tuning the %R1 and
%X,
、
the rated slip
Frequency with the
motor stopped
,
Tuning the no-load
current and magnetic
saturation factor, with
the motor running(at
50% of the base
frequency.)
Tuning the %R1 and
%X, with the motor
stopped.Tuning the
no-load current and
magnetic saturation
factor, with the motor
running at 50% of
the base frequency.
Tuning the rated slip
frequency, with the
motor stopped.
Under no-load
status (motor
idling, not connect
to the mechanical
transmission part)
Tuning with load
applied decreases
the tuning
accuracy.
03
.
04*
Data
Auto-
Tuning
type
Motor parameters
subjected to tuning
Tuning Action
Selection
Condition of Auto-
tunning type
Control
Method
with
-out
PG
V/f
PG
× ○ ○
○ × ×
○ △ △
Tuning with the
motor stopped
Cannot rotate
the motor
Tune
while
the
motor
stops
Tune
while
the
motor
is
rotating
under
V/f
control
Tune
while
the
motor
is
rotating
under
Vector
control
3
2
1
○
: Auto-tuning available
△
: Using with additional conditions
×
: Auto-tuning unavailable
All types of control methods are displayed in “V/f:V/f control”, “No PG: vector control without sensor”,
and “PG: vector control with sensor”.