6
(2) Installation Clearance
Make sure that the minimum clearances indicated in Figure 2.1 and Table 2.3 are maintained at all
times. When mounting the inverter in the panel of your system, take extra care with ventilation inside
the panel as the surrounding temperature easily rises. Do not mount the inverter in a small panel with
poor ventilation, it’s easy to cause failure due to the inverter overheating.
(3) Installing two or more inverters
When installing several inverters in the same unit or panel, install them side by side. When one must
be installed above the other, be sure to separate them with a partition plate, or the like, so that any
heat radiating from an inverter will not affect the one/s above.and pay attention to put the position for
cooling , must install cooling fans on the case, to make the inverter surrounding temperature below
50
℃
for the principle. As long as the surrounding temperature is 40
℃
(104
o
F) or lower, inverters of
22kW or below can be mounted side by side without any clearace between them.
Inverter capacity
1.5kW
2.2~22kW
30~315kW
A
50
10
50
B
100
Table 2.3 Installation Clearance
(
mm
)
B
B
A
A
Figure 2.1 Installation diagrammatic drawing
IN
S
ID
E
T
H
E
C
A
B
IN
E
T
(FALSE)
AIR EXCHANGE FAN
IN
S
ID
E
T
H
E
C
A
B
IN
E
T
INSIDE THE
CABINET
(CORRECT)
(FALSE)
(CORRECT)
IN
S
ID
E
T
H
E
C
A
B
IN
E
T
AIR EXCHANGE FAN
C