SAMLEX AMERICA INC. | 99
SECTION 5 |
Battery Charging in Evolution™ Series
b) Wiring Connection:
Output from the SSR Terminals on the Lithium Battery BMS should be wired to the RJ-
45 Jack marked “Battery Temp. Sensor” (
6, Fig 2.1
) as follows:
• Connect terminal marked “+” on the SSR (
Drain of Mosfet switch inside SSR
) to any of pins 1/2/3/4 of
RJ-45 Jack (
Pinout shown at Fig 5.6
)
• Connect terminal marked “-” on the SSR (
Source of Mosfet switch inside SSR
) to any of pins 5/6/7/8 of
RJ-45 Jack (
Pinout shown at Fig 5.6
)
1 2 3 4 5 6 7 8
+5V
Internal
Schematic
of EVO
TM
Batt Temp
to DSP
1K
5.1K
Fig 5.6 Pinout of RJ-45 Jack marked "Battery Temp. Sensor" on the Front Panel of EVO
TM
(6, Fig 2.1)
When the Drain-Source terminals of the BMS close, Pins 1/2/3/4 and 5/6/7/8 of RJ-45 Jack will be shorted. The following
actions will be activated in EVO
TM
:
• EVO
TM
in Charging Mode:
Charging will stop (
Internally, the EVO
TM
will be in Charging Mode, but the charging
current will be reduced to 0A
). Charging Mode Screens in EVO-RC-PLUS Remote Control will show message
(Refer to Section 3.6.8.3 of EVO-RC-PLUS Remote Control Manual).
• EVO
TM
in Inverting Mode:
Inverting will stop (
Internally, the EVO
TM
will enter Standby Mode
).Inverting Mode
Screens in EVO-RC-PLUS Remote Control will show message
(Refer to Section 3.6.9.3 of EVO-RC-PLUS Remote
Control Manual)
.
5.12 OPERATING MODE OPTION - “CHARGER ONLY”
In Off-grid DC powered homes, for efficiency consideration, all lighting and other loads / appliances may be powered
from 12V batteries that are primarily charged through solar / wind power. Generator backup is used for powering AC
to DC battery charger for charging the batteries during extended periods of cloudy / no wind conditions. To meet this
requirement, the EVO
TM
can be programmed to operate as a battery charger ONLY i.e. when AC input power is available
within the programmed limits of voltage and frequency, charging will take place and AC input will be passed through to
the load(s). The unit will not transfer to Inverting Mode if AC input fails or is outside the programmed limits of voltage
and frequency.
For further details refer to Section 4.4.2.13.1 in EVO-RC-PLUS Remote Control Manual.