SAMLEX AMERICA INC. | 105
SECTION 6 |
Operation, Protections and Troubleshooting
TABLE 6.2 PROGRAMMABLE AND DEFAULT PARAMETERS: PARAMETER GROUP NO.1 "CHARGING CURVE"
(For detailed information on parameters in this Table, refer to Section 4.4.2 of the Owner's Manual for Remote Control
EVO-RC-PLUS)
Parameter
Programming Range
(Programming requires optional Remote Control
Model EVO-RC-PLUS)
Default
“BULK CURRENT” (See NOTES 1 & 2)
(
Bulk Charge Current “Io”
)
60A
20A
“ABSORP VOLTAGE”
(
Absorption Voltage
)
48.00V - 64.00V
57.60V
“EQUALIZE VOLTAGE”
(
Equalization Voltage
)
56.00V - 66.00V
57.60V
“FLOAT VOLTAGE"
(
Float Voltage
)
48.00V - 60.00V
54.00V
“COMPENSATE”
(
Temperature Compensation
)
3mV to 5mV /C/Cell
4mV /C/Cell
“BATT OVER VOLT”
(
Battery Over Voltage Shutdown
)
56.00V - 70.00V
64.00V
“RESET VOLTAGE”
(
Reset voltage for "BATT LOW
VOLTAGE" condition
)
48.00V - 70.00V
56.00V
“LOW VOLT ALARM”
(
Battery Low Voltage Alarm
)
38.00V to 54.00V
44.00V
“BATT LOW VOLTAGE”
(
Battery Low Voltage Shutdown
)
>36.00V to 52.00V
42.00V
“LV DETECT TIME”
(
Time to qualify "BATT LOW VOLTAGE"
condition
)
0 - 600 sec
10 sec
“LV CUT OFF TIME”
(Time in "BATT LOW VOLTAGE"
condition to trigger complete
shutdown)
0 - 7200 sec
1200 sec
“EQUALIZE-4STAGES”
(
4 Stage Adaptive Equalization On/ Off
)
0 = No
1 = Yes
0 = No
"MODE"
0 = Normal…AC input priority (Off-Line)
1 = On-Line…Inverter priority
2 = Charger Only…Charging & AC bypass only, no inverting
0 = Normal
"ONLINE OPTION"
(
Available only when parameter
"MODE" is set to option "1=On-Line"
)
0 = Option 1
1 = Option 2
0 = Option 1
Table continues on next page
}