108 | SAMLEX AMERICA INC.
SECTION 6 |
Operation, Protections and Troubleshooting
TABLE 6.6 PROGRAMMABLE AND DEFAULT PARAMETERS: PARAMETER GROUP NO.5 "OTHER FUNCTIONS"
(For detailed information on parameters in this Table, refer to Section 4.8.2 of the Owner's Manual for Remote
Control EVO-RC-PLUS)
Parameter name
Setting range
Default Value
“POWER SAVING”
1 = Enable 0 = Disable
0 = Disable
“ENTER POINT”
4 – 50W
8W
“WAKE UP POINT”
5 – 50W
12W
“REMOTE SWITCH”
For ON /OFF control
through external 12V
signal fed to Remote
ON / OFF terminals on
the Front Panel (15,
Fig 2.1)
0 = Button Type
: 12V signal is fed through Push Button
Type of Switch
Pressing of Push Button > 2 sec will switch the unit ON
When ON, pressing Push Button > 5 sec will turn the
unit OFF
1 = Switch Type:
12V signal is fed through contacts of
Toggle Type of Switch or relay contact
ON condition (
contacts closed
) will turn the unit ON
OFF condition (
contacts open
) for 2 sec will switch
the unit OFF
0
= Button Type
CAUTION!
ON/OFF Logic also
controls the operation of the ON/
OFF Button on the front panel
(
11, Fig 2.1
). The Default setting is
"Button Type".
If the ON/OFF Control is changed
to external "Remote Switch", it will
not be possible to switch ON/OFF
the EVO
TM
Inverter/Charger from the
front panel ON/OFF Push Button
because it will work with Switch Type
Logic. It will be ON only as long as
the Push Button is kept pressed and
will switch OFF when released.
“RELAY FUNCTION”
(
for Status Relay
)
0 = Charge / Other
OFF in "Charging" Mode
ON in other Modes i.e. "Inverting", "Power Saving" or
"Standby"
1 = Normal / Fault
OFF in normal operating conditions
ON in Fault Modes
2 = Generator 0
ON when batteries drop to "LOW VOLT ALARM" or lower
for period = "GS DETECT TIME" - Initiates Generator start
OFF after batteries are charged till the end point of the
programmed option under parameter "CHARGING
PROFILE"
[See Section 4.8.2.5.2.1 of EVO-RC-PLUS Remote Control
Manual]
. When the relay switches OFF, it initiates Generator
Stop.
3 = Generator 1
ON when batteries drop to "LOW VOLT ALARM" or lower
for period = "GS DETECT TIME" - initiates Generator start
OFF when batteries are charged to "RESET VOLTAGE" for
period = "GEN OFF DELAY" - initiates Generator stop
4 = Generator 2
ON when batteries drop to "LOW VOLT ALARM" or lower
for period = "GS DETECT TIME" - initiates Generator start
OFF after period = "GEN ON TIME" from the time relay
switched ON - initiates Generator stop
2
= Generator 0
Table continues on next page
}