SAMLEX AMERICA INC. | 103
SECTION 6 |
Operation, Protections and Troubleshooting
Manual for Remote Control EVO-RC-PLUS
)
• When the EVO
TM
is in Off condition, momentary feeding of +12V signal through the external Push Button for > 2
sec will turn the unit On.
The EVO™ will remain ON even when the Push Button is released
• When the EVO
TM
is in On condition, momentary feeding of +12V signal through the external Push Button for > 5
sec will turn the EVO
TM
OFF.
NOTE:
If the external Push Button is pressed for < 5 sec, the unit will NOT switch Off
6.2.2 Switch Type On/Off Control Using +12V Signal
For this type of control, programming parameter "REMOTE SWITCH" should be set to option "1=Switch Type" (
See
Section 4.8.2.4 of Owner's Manual for Remote Control EVO-RC-PLUS
).
This type of ex12V signal format is used when the +12V signal (
+9 to 15 VDC, < 10mA
) is fed through an
external, series connected On/Off Toggle / Rocker Switch or Relay contact (
+12V signal will be fed continuously when
the switch in ON condition / Relay contact is closed and +12V signal will be removed when the external On/Off switch
is in OFF condition or the Relay contact is open
). Control logic used is as follows;
• When the external On/Off Switch is turned On or when the Relay contact is closed, cont12V control
signal will be made available and the EVO
TM
will turn ON. EVO
TM
will remain On as long +12V control signal is
available through the On condition of the external On/Off Switch or the closed Relay contact
• When the external On/Off Switch is turned Off or if the Relay contact opens, the +12V signal will be removed and
the EVO
TM
will switch Off
!
CAUTION!
When “Switch Type” of ON/OFF control described at Section 6.2.2 is selected, the ON/OFF Button on the
front panel of the unit (12, Fig 2.1) should NOT be used to turn ON or turn OFF the unit. The front panel
ON/OFF Push Button will now follow the above “Switch Type” control logic wherein the unit will remain
ON only as long as the Button is kept pressed and will turn OFF in 2 seconds after it is released.
!
ATTENTION!
Lorsque « Switch Type » de ON/OFF contrôle décrit ci-dessus est sélectionnée, le bouton on/
off sur le panneau avant de l’unité (12, Fig 2.1) ne devraient pas servir à allumer ou éteindre
l’appareil. La façade, bouton poussoir On/Off suivra désormais la logique de contrôle ci-dessus
« Switch Type » dans lequel l’appareil demeurera allumé aussi longtemps que la touche est
maintenue enfoncée et s’éteint après 2 secondes après que qu’il est libéré.
6.3 OPERATIONAL INFORMATION THROUGH LEDS AND BUZZER
Table 6.1 shows the operational states of the unit indicated by the following LEDs on the front panel of the unit and Buzzer:
o
Blue LED marked “ON” (12, Fig 2.1)
o
Red LED marked “Fault” (13, Fig 2.1)