SAMLEX AMERICA INC. | 55
SECTION 3 |
Installation
• The “INPUT GND” Terminal (
8A, Fig 3.9
) of the AC Input / Output Terminal Block in EVO™ gets connected to the
Grounded Bus Bar (
G-B
) in the Grid Electrical Panel (
AC PANEL 1
) through the grounding wire of AC input connection
• The Grounded Bus Bar (
G-B
) in the Grid Electrical Panel (
AC PANEL 1
) is bonded to Earth Ground through the
Grounding Electrode (
GE
) / “Ground Rod” of the premises
b) AC Output Grounding:
The metal chassis of the AC load(s) gets connected to the Grounding Electrode (
GE
) /
“Ground Rod” of the premises as follows:
• The metal chassis of the AC load(s) connected to the EVO™ is connected to the Grounded Bus Bar (
G-B
) of
the Electrical Sub Panel for EVO™ Output
• Grounded Bus Bar (
G-B
) of the Electrical Sub Panel for EVO™ Output (
AC PANEL 2
) is connected to metal chassis
of EVO™ through the “OUTPUT GND” Terminal (
8B, Fig 3.9
) of the AC Input / Output Terminal Block in EVO™.
• The metal chassis of EVO™ is connected to the “INPUT GND” Terminal (
8A, Fig 3.9
) of the AC Input / Output
Terminal Block in EVO™
• The “INPUT GND” Terminal (
8A, Fig 3.9
) of the AC Input / Output Terminal Block in EVO™ gets connected to the
Grounded Bus Bar (
G-B
) in the Grid Electrical Panel (
AC PANEL 1
) through the grounding wire of AC input connection
• The Grounded Bus Bar (
G-B
) in the Grid Electrical Panel (
AC PANEL 1
) is bonded to Earth Ground through the
Grounding Electrode (
GE
) / “Ground Rod” of the premises
3.14.3 Switching Of Bonding Of Output Neutral To Chassis Ground
As required by NEC, automatic switching of bonding between the Output Neutral and Chassis Ground has been provided in
EVO™ through “Output Neutral and Chassis Ground Bond Switching Relay” (
RY-5 in Fig 4.1
). Switching is carried as follows:
• When operating as an inverter, the current carrying conductor of the Inverter Section that is connected to the
Output Neutral terminal of the EVO™ is bonded to the metal chassis of EVO™ by the “Output Neutral to Chassis
Ground Bond Switching Relay” (
RY-5 in Fig 4.1
). As the metal chassis of EVO™ is in turn bonded to the Earth
Ground (
in shore installations
), this current carrying conductor of the Inverter Section (
connected to the Output
Neutral Terminal
) will become the Grounded Conductor (
GC
) or the Neutral of the Inverter Section.
• When in Charging Mode, the Neutral conductor of Grid power or Generator will be connected to the Output
Neutral terminal of EVO™. At the same time, the “Output Neutral to Chassis Ground Bond Switching Relay” (
RY-5
in Fig 4.1
) will unbond (
disconnect
) the Output Neutral connector of EVO™ from the metal chassis of EVO™. This
will ensure that the Grounded Conductor (
GC
) i.e. the Neutral of the Grid power is bonded to the Earth Ground at
one single point at the location of the AC Power Distribution System of the Marina / RV Park / Shore Power.
• Disabling Neutral to Ground Bond:
In some applications, the Output Neutral of EVO™ may be required to
remain isolated from the chassis/Ground at all times. For this, automatic Ouput Neutral to Chassis Ground bond can
be disabled by disconnecting the Insulated Male/Female Quick Disconnect located in the AC wiring compartment.
For more details, refer to Sections 4.5.2(D) and 4.5.2(E).
3.15 BATTERY TEMPERATURE SENSOR: MODEL NO. EVO-BCTS
3.15.1 Temperature Compensation of Battery Charging Voltages
Please refer to Section 5.5 for detailed information on temperature compensation of battery charging voltages
using Battery Temperature Sensor EVO-BCTS.