TITAN
-
manuale di installazione, conduzione e manutenzione
-
Installation and maintenance manual
23
Destination of use and generalities
The
TITAN
units are designed for the
air treatment in the air conditioning systems
and they consist of equipment dimensioned in
function of the specific needs of the system which they are intended for. Their only serial element is the construction system, while their
technical performance characteristics are customized and specified in the annexed documents such as specification data sheets, layouts,
electric diagrams, etc. that are their integrating parts.
SABIANA
bears neither responsibilities nor bounds, of any kind, for any use different from the one specified above.
Particular attention shall be paid when choosing the installation place of the
TITAN
Air Handling Unit (hereunder called also UTA) and the
atmosphere in which it is installed must not be explosive or corrosive for the materials which build up the unit.
The careful reading of this manual permits to carry out the correct installation, precise setup and effective maintenance. together with its
annexes, the manual shall be kept with care and made available for every reference.
All the installation, test and servicing operations must be carried out by qualified personnel, that is technically trained and competent.
Any tampering or electrical or mechanical change, which are not previously agreed upon and authorized, cancel the Warranty of the unit.
Always observe the safety standards in force on the installation place and the provisions set by the Operative Management of the site.
Before starting up the equipment check that the
characteristics of the power supply lines comply with the
rated values indicted on the labels positioned next to any
power equipment (e.g.: fan motors, electric heating
resistances, etc.).
In case of failure or maintenance, the power supply
equipment must be always switched off. Moreover, for any
replacement of components which should be carried out,
always apply to
our main office
or an
Authorized
Servicing Center of
SABIANA
that makes use of
original spare parts
.
The dismissed packing material (plastic, wood, polystyrene,
polyurethane, cardboard, staples, nails, etc.) must be kept
out of the reach of children for it might be dangerous for
their health and it must be disposed of or recycled correctly in
compliance with the local standards in force.
SABIANA
disclaims any responsibility for any damage to
people or thing that might come, either directly or indirectly,
from the disregard of these instructions.
Standards and certifications
The
TITAN
air handling units are manufactured in
the full compliance with Standard:
UNI EN 1886
- June
2000 -
Mechanical performance
.
and classified according to Standard:
UNI EN 13053
- September 2007
-
classifications and performances for units,
components and sections
with certificate issued by
Authorized Body, certifying the characteristics shown in the
table
SABIANA
is certified according to
UNI EN ISO 9001
since
1996
All the
SABIANA
products are provided with the
CE
mark,
for they are manufactured in compliance with the Directives
of the European Union and relevant National Laws; therefore
each one of them comes complete with the relevant
"statement of conformity"
• casing strength
D1
• casing air leakage at -400 Pa
L3
• casing air leakage at +700 Pa
L3
• filter bypass leakage (at + and - 400 Pa)
G1 - F9
• thermal transmittance
T2
• thermal bridging factor
TB3
dB 13,4
dB 16,5
dB 14,6
dB 13,4
dB 15,9
dB 26,3
dB 32,8
125
250
500
1K
2K
4K
8K
Frequency
Hz
50 mm thick panels
with polyurethane
P
OLYURETHANE
INSULATION
S
OUND
A
TTENUATION
S
PECIFICATIONS
OF
THE
CASING
ACCORDING
TO
UNI-EN 1886
TUV SUD – report test number MB747
• casing strength
D1
• casing air leakage at -400 Pa
L3
• casing air leakage at +700 Pa
L3
• filter bypass leakage:
+ 400 Pa =
G1 - F9
/ - 400 Pa =
G1 - F7
• thermal transmittance
T3
• thermal bridging factor
TB3
dB 15,6
dB 19,8
dB 18,3
dB 19,5
dB 20,5
dB 28,6
dB 35,3
125
250
500
1K
2K
4K
8K
Frequency
Hz
50 mm thick panels
with mineral wool
M
INERAL
W
OOL INSULATION
S
OUND
A
TTENUATION
S
PECIFICATIONS
OF
THE
CASING
ACCORDING
TO
UNI-EN 1886
TUV SUD – report test number MB748