MRL100 / 942 / 699Plus 

 A1- Instruction Manual

  

Digital load / weight measuring system 

S2Tech srl

  Via Imperia, 28  Milano – ITALY 

Tel: +39 02 8910142 Fax: + 39 02 89124848     

e-mail: 

[email protected]

  

www.s2tech.it 

 

Version : UK 2r7 dated 25/06/15 
Page: 3/4 

 

Notice: 

The information in this manual is subject to change without notice.S2Tech  shall  not be  liable  for  technical  or  editorial  errors  or  omissions  contained  herein,  nor  for  incidental  or  consequential damages  resulting  from  the  furnishing, performance,  or  use  of  this material.      This  manual contains information protected by 

copyright. No part of this manual may be photocopied, or reproduced in any form, or translated without prior written consent from S2Tech.  

 

Z:\Manuali\LM MRL100_942_699A1\Traduzioni Maggio 2015\LM MRL_942_699A1 V2r7 UK .docx 

 

F) 699 Instrument configuration – 

MANU

 procedure 

0) Once 

MultiRope MRL100

 system has been installed, enter this procedure by : 

 

powering the 699 unit, while pressing 

+

C

 buttons 

 

using RESET pushbutton, while pressing 

+

C

 buttons 

Display will show 

MANU

 to confirm procedure activation. 

Use 

 or 

 to view available parameters. 

Use 

E

 to view and modify existing numeric parameter or to confirm changes to 

parameter.  699 unit indicate that new parameter has been accepted by showing, 
briefly, 

MEMO

 and then displaying again the parameter’s name. 

Use 

C

  to  end  calibration  and  start  load  measurement  or  to  abort  changes  to 

numeric parameter, maintaining the existing value. 
To modify numeric parameter use 

 to increase or 

 to decrease value of one 

unit.  

+

 E

 increase value of 10 and then 100 units while 

+

 C

 decreases of 

10 and then 100 units. 

 

 

OPTIONAL: 

Press 

C

 - with empty car- 

after SAVE and reboot of 

the 699Plus, after 

calibration. 

1) 

TARE

: a tare value is set, as current lift’s own weight (always set to 0); 

use 

the lift for some runs, at maximum load  (also jump on the lift), prior this 
measurement;

 press 

E

 to start count down (60 sec; display shows from 

T-60

 to 

T-0

 to indicate remaining delay) to allow technician to move away form lift (no 

load  on  lift’s  floor  until  measurement  is  taken).    Tare  measurement  is 
completed after 

MEMO

 is displayed and 

TARE

 is shown again.  

2) 

HI

:  Used  to  acquire  measurement  corresponding  to  the  reference  known 

weight,  placed  in  the  middle  of  lift’s  floor.  Enter  the  weight  value,  in  Kg  or 
other engineering units, and press 

E

 to start count down (60 sec; display shows 

from 

T-60

  to 

T-0

  to  indicate  remaining  delay).    HI  measurement  is  completed 

after 

MEMO

 is displayed and 

Hi

 is shown again.  Calibration quality will increase 

by using a weight of around 50 % of lift’s rated capacity (or as near as possible 
to lift’s capacity). 
Measurement  performed  by  the  699F  unit  will  be  shown  in  the  same 
engineering  unit  used  for  HI  value  (Kg,  Lbf,  N,  etc.  –  Measurement  Unit  not 
shown). 
3) 

FSCA

: maximum lift’s rated capacity, in Kg or other engineering unit. 

Default 

value = 0

 

4) 

LEV1

:  alarm  level  value,  expressed  in  percentage  of  the  FSCA  value,  to 

activate Relay 1 (modifiable value).  

Default value = 80 % FSCA

5) 

LEV2

:  alarm  level  value,  expressed  in  percentage  of  the  FSCA  value,  to 

activate Relay 2 (modifiable value).  

Default value = 110 % FSCA.

 

6) 

LEV3

: alarm level value, expressed in percentage of the FSCA value, to 

activate Relay 3 (modifiable value).  

Default value = 5 % FSCA

This parameter is considered by 699 only if Relay 3 is installed (

option

). 

7) 

CHNC

:  (option)  Towed  chain  compensation  and  relays  block  are  inactive 

(default) if CHNC=0; active if CHNC=1.  Parameter is available only if digital 
input 1 and digital input 2 are installed. 

ATTENTION:

  

When the programming procedure is ended by pressing the 

C

 button and the unit enters 

into the normal measurement mode (i.e. MCAL), it is possible that with empty car a value different from 
zero is shown, or that the units displays a value different from the used calibration load.

 

Please unload the car and press the 

C

 button once, confirming the weight for the empty car.  

G) Towed chain compensation and relays block function 

Towed chain and relays block function are activated as follows: 

1.

 

When  doors  are  closed,  feed  between 

INPUT1

  (terminal  5)  and 

EXGND

  (terminal  6  =  GND/common 

reference) a voltage coming from door relay where: 

0 Vac/dc = lift DOOR OPEN

+12/24Vac/dc = lift DOOR CLOSED.

 

2.

 

In case of black out (no power supply fed to  699), cabin is to be moved to lowest floor, in order to align 
chain compensation function. 

 

H) 699 Relay test procedure 

It is possible to verify functionality of all the installed relays by keeping pressed, at power on or after having pressed 
the reset button, 

+

 E

When  699

plus

  unit  enters  this  procedure  display  shows  TREL  and  relay  activation  (if  present)  can  be  tested  by 

pressing 

 to test Relay 1, 

 to test Relay 2 or 

E

 to test Relay 3. 

Press 

Reset

 button to return to normal measurement operation. 

 

I) 699 Plus electronics Analog Output setting (Optional) 

Making reference to the 699 customization procedures, parameter setting for analog output signal must be done considering the 
following flowchart: 

 

Note

: the analog output circuit provides an analog output signal for all operative modes. The firmware version is to be at least 

1.17 or higher. To obtain a reversed 10V to 0V output, calibrate DACL with high engineering units (measuring range) while on 
DACH enter lower ones.     Analog output signal connection is as per attached connection scheme. 

 

Содержание MRL100

Страница 1: ...n elevator ropes 1 Apply C screws to A sensor like shown in picture 2 Position the MultiRope MRL100 sensor A close to the ropes parallel to the cabin roof and insert all ropes in the slot between the...

Страница 2: ...al Relay 2 Normally Closed contact 12 Screw Terminal Relay 2 Common contact 13 Screw Terminal Relay 1 Normally Open contact 14 Screw Terminal Relay 1 Normally Closed contact 15 Screw Terminal Relay 1...

Страница 3: ...ound 50 of lift s rated capacity or as near as possible to lift s capacity Measurement performed by the 699F unit will be shown in the same engineering unit used for HI value Kg Lbf N etc Measurement...

Страница 4: ...s analog output signal it is mandatory to connect 699Plus analog output to the Inverter s input considering its input characteristics A Inverter with floating input 2 wire connection E g Inverter 699P...

Страница 5: ...Applicare le viti C al sensore A come da figura 2 Posizionare il sensore MultiRopeMRL A vicino alle funi parallelo al tetto della cabina inserire tutte le funi nello spazio tra le viti senza sovrappor...

Страница 6: ...e Relay 1 contatto Normalmente Chiuso 15 Terminale a vite Relay 1 contatto comune 16 Terminale a vite alimentazione al sensore 17 Terminale a vite alimentazione al sensore 18 Terminale a vite segnale...

Страница 7: ...o visualizzate nella stessa risoluzione ed unit di misura usata per la memorizzazione di HI le unit ingegneristiche Kg Lbf N etc non sono mostrate 3 FSCA valore di pieno carico dell ascensore in Kg od...

Страница 8: ...nalogica del 699Plus all ingresso dell inverter tenendo conto delle caratteristiche di quest ultimo A Inverter con ingresso flottante connessione a 2 fili E s Inverter 699Pus A1 Pin 11 Comune analogic...

Страница 9: ...en 1 Die Schrauben C wie in der Abbildung angegeben am Sensor A anbringen 2 Den Sensor MultiRopeMRL A nahe an den Seilen parallel zum Kabinendach einf hren Alle Seile in den Zwischenraum zwischen den...

Страница 10: ...Bezug auf gemeinsam 7 Terminal mit Schrauben Relais 3 Kontakt normaler Weise offen 8 Terminal mit Schrauben Relais 3 Kontakt normaler Weise geschlossen 9 Terminal mit Schrauben Relais 3 Kontakt gemei...

Страница 11: ...ndet wird so nah wie m glich an der Volllast Die Messungen des digitalen Instruments 699F werden in der gleichen Aufl sung und Messeinheit angezeigt wie die f r das Speichern von HI verwendeten die te...

Страница 12: ...der analoge Ausgang der 699Plus an den Eingang des Inverters angeschlossen werden wobei die Merkmale dieses letztgenannten zu ber cksichtigen sind A Inverter mit erdfreiem Eingang Anschluss mit 2 Dr...

Страница 13: ...is C au capteur A selon la figure 2 Positionner le capteur MultiRopeMRL A pr s des c bles parall lement au toit de la cabine installer tous les c bles dans l espace entre les vis sans les superposer 3...

Страница 14: ...alement ferm 9 Vis terminale Relais 3 contact commun 10 Vis terminale Relais 2 contact normalement ouvert 11 Vis terminale Relais 2 contact normalement ferm 12 Vis terminale Relais 2 contact commun 13...

Страница 15: ...s la m me r solution et unit de mesure utilis es pour la m morisation d HI les unit s d ing nierie Kg Lbf N etc ne s affichent pas 3 FSCA valeur de charge pleine de l ascenseur en kg ou dans une autre...

Страница 16: ...eur en tenant compte des caract ristiques de ce dernier A Inverseur avec entr e flottante connexion 2 fils E s Inverseur 699Pus A1 Pin 11 Analogique Commun AGND GND Pin V2 Entr e analogique Analog Sig...

Страница 17: ...olocar el sensor MultiRope MRL A cerca de los cables paralelo al techo de la cabina introducir todos los cables en el espacio entre los tornillos sin superponerlos 3 Cuando los cables se encuentran en...

Страница 18: ...a 6 Terminal de tornillo Entrada salida referencia com n 7 Terminal de tornillo Rel 3 contacto Normalmente Abierto 8 Terminal de tornillo Rel 3 contacto Normalmente Cerrado 9 Terminal de tornillo Rel...

Страница 19: ...nstrumento digital 699F se visualizan en la misma resoluci n y unidad de medida para la memorizaci n de HI no se muestran las unidades de ingenier a Kg Lbf N etc 3 FSCA valor de plena carga del ascens...

Страница 20: ...ter teniendo en cuenta las caracter sticas de ste ltimo A Inverter con entrada flotante conexi n de 2 cables Ej Inverter 699Pus A1 Pin 11 Com n anal gico AGND GND Pin V2 Input Anal gico Analog Signal...

Страница 21: ...nuali LM MRL100_942_699A1 Traduzioni Maggio 2015 LM MRL_942_699A1 V2r7 RU docx A Multirope MRL100 2 8 8 8 DIN 933 ISO 4762 M8 A2 C 1 MultiRope MRL 1 B A C F 3 6 6 5 F 4 6 6 5 F 6 6 6 5 B A MRL100 72 B...

Страница 22: ...6 LIFTSENTRY 15 CE EN 61326 1 1997 A1 1998 A2 2001 A3 2003 EN 61000 6 2 2001 EN 61000 3 2 2000 A2 2005 EN 61000 3 3 1995 A1 2001 EN 61000 4 2 1995 A1 1998 A2 2001 EN 61000 4 3 2002 A1 2002 EN 61000 4...

Страница 23: ...L_942_699A1 V2r7 RU docx F 699 MANU 0 MultiRope 699 C RESET C MANU E 699 MEMO C E 10 100 C 10 100 C SAVE 699Plus 1 TARE 0 TARE E 60 T 60 T 0 MEMO TARE 2 HI E 60 T 60 T 0 HI MEMO HI 50 100 699F HI 3 FS...

Страница 24: ...x DMOD DMODE 1 DMODE 0 0 10 699Plus A1 00 03 010 0010 J 00 03 010 0010 A1 0 10 AGND 699Plus A 2 699Pus A1 11 AGND GND V2 B 3 699Plus 1 JP11 1 JP11 2 AGND 699Plus 2 JP11 3 699Pus A1 JP11 1 0V JP11 2 AI...

Отзывы: