Input power shall be larger than the actual power consumption of entire system. For example, the
RG-S8610E chassis is installed with two M8600E-CM , two
M8600E-48XS-DB and two M8610E-FE-D I
modules
, the total power consumption of the device would be: 2 x 44W (M8600E-CM)+ 2 x 232W
(M8600E-48XS-DB) + 3 x174W (M10-FAN-R)
+ 219W (M10-FAN-F) +2 x 107W (M8610E-FE-D I) = 1507W
.
It is recommended that you adopt two RG-PA1600I or two RG-PD1600I modules.
The following table lists the power consumption of each module:
RG-S8600E Series Modules
Maximum Power Consumption (W)
M8600E-CM
40
M8600E-08XS-ED
85
M8600E-08XS-EF
<120
M8600E-24GT20SFP/4XS-ED
<100
M8600E -48GT-ED
<95
M8600E -48GT-EF
<125
M8600E -48GT-P-ED
No PoE or PoE+ supply: <95W;
PoE supply: <95W+15.4W x N (N stands for the
number of PoE ports in use, no greater than 48);
PoE+ supply: <95W+30W x N (N stands for the
number of PoE+ ports in use, no greater than 48)
M8600E -44SFP/4XS-ED
<135
M8600E -44SFP/4XS-EF
<175
M8600E -48XS-DB
<232
M8600E -12QXS-DB
<200
M8600E -24XS4QXS-DB
<208
M8600E-24GT/8SFP-EB
<58
M8600E-24SFP/8GT-EB
<72
RG-WALL 1600-B-ED
<190
M8600E -FE-D
I
<107
M05-FAN
<288
M07-FAN
<432
M10-FAN-F <219
M10-FAN-R <174
The RG-S8600E provides N+M redundancy of power supply. You are recommended to use multiple power
supplies for the equipment to ensure its continuous and stable operation by avoiding the impact of
unexpected power failures on the equipment.
When the dual power supply is applied, the type of the power supply should be identical.
System Grounding Requirements
A good grounding system is the basis for the stable and reliable operation of the RG-S8600E. It is the key to prevent
lightning stroke and resist interference. Please carefully check the grounding conditions on the installation site according
to the grounding requirements, and perform grounding properly as needed.
Safety Grounding
The equipment using AC power supply must be grounded by using the yellow/green safety grounding cable. Otherwise,
when the insulating resistance decreases the power supply and the enclosure in the equipment, electric shock may occur.
Содержание RG-S8605E
Страница 1: ...RG S8600E Series Switches Hardware Installation and Reference Guide V1 09...
Страница 63: ...Figure 2 2 Preventing EMI on RG S8607E Figure 2 3 Preventing EMI on RG S8610E...
Страница 86: ...Figure 3 21 Grounding Point on the Rear of the RG S8610E Switch...
Страница 116: ...Figure 7 12 Replacing the Module for RG S8610E...
Страница 120: ...Note A Fan modules to be removed B Fan modules to be installed...
Страница 132: ......