Swell End Voltage
Swell end voltage is configured as percentage to reference voltage. Swell end event is generated when
measured voltage returns below the end voltage. Hysteresis voltage exists between start voltage and end
voltage to prevent a large number of short events and minimum Hysteresis is 1%. In other words, end voltage
can be configured at least 1% lower than start voltage. If start voltage is configured lower than end voltage,
end voltage is automatically reconfigured 1% lower than start voltage.
Setup range
Description
101.0 - 998.0% [default 108.0%]
Percentage of Swell reference voltage
Swell end voltage display
VL-N [Line-to-neutral]
3P4W/1P3W/1P2W connection
VL-L[Line-to-line]
3P3W connection
[d][d][d].[d] V/kV
Swell reference voltage * Percentage
Fig 4.24 Swell Event Setup[3-phase 4-wire]
Reference voltage: Line-to-line voltage
380V setting
Fig 4.25 Swell Event Setup[3-phase 3-wire]
Reference voltage: Line-to-line voltage
380V setting