Chapter 2 Installation
Accura 2300/2350 User Guide
Page 42
ⓒ
2011 Rootech Inc. All Rights Reserved
Installation Diagram
Accura 2300/2350-3P[1P] Power Measuring Module
The following shows a diagram example of Accura 2300/2350 installation.
Fig 2.25 Accura 2300/2350-3P[1P] Power Measuring Module Installation Diagram
1. If rating current exceeds 250A, Accura 2350-3P-CT5A-75 using external CT[secondary rating 5A] should be used.
2. Packaged with device. Core conductor of 6C telephone line should be minimum 0.128mm
2
[26 AWG]. It is recommended
that distance from power line is 5mm or more so that interference caused by noisy power line will not occur.
Installation
Front panel
Accura 2300
Distribution panel digital power meter
Incoming feeder
Accura 2350-3P-CT5A-75
1
Three-phase power measuring module
Branch load
Accura 2350-3P
Three-phase power measuring module
Accura 2350-1P
Single-phase power measuring module
TM-3P
Three-phase terminal
TM-1P
Single-phase terminal
Communication
6C Telephone Line
2
Only for internal communication
Use transformer
for more than AC 265V