Chapter 3 Accura 2350 Operation/Setup
Accura 2300/2350 User Guide
Page 114
ⓒ
2011 Rootech Inc. All Rights Reserved
Rating Current Setup
The rating current of Accura 2350 single-phase power measuring module is selected as follows.
Item
Range
Description
Rating current
[d][d][d]
1
Rating current setup
1 – Max. rating current [default: Max. rating current]
2
1. d
decimal number.
2. The maximum rating current of Accura 2350 single-phase power measuring module is as follows. The rating current is
set to the maximum rating current when it exceeds the maximum rating current.
Module
Max. rating current
Single-phase
Accura 2350-1P-250A-105
250A
Accura 2350-1P-125A-60
125A
Accura 2350-1P-100A-50
100A
Accura 2350-1P-60A-50
60A
Accura 2350-1P-50A-35
50A
Accura 2350-1P-30A-35
30A
Single-phase single-hole
Accura 2350-1PSH-50A-35
50A
Accura 2350-1PSH-30A-35
30A
Split-core single-phase
Accura 2350-1PSC-250A-105
250A
Accura 2350-1PSC-125A-60
125A
Accura 2350-1PSC-60A-50
60A
Leakage Current Threshold Setup
Leakage current measurement is supported by installing an external ZCT[voltage-type] and connecting the
ZCT output voltage to the ZCT input terminal of Accura 2350 module.
If the leakage current threshold is set to “oFF”, leakage current measurement is disabled and the measured
value is not displayed. When the leakage current threshold is set, leakage current is measured and displayed.
Also, it detects the exceeding of threshold value and processes leakage current event in Accura 2300
according to whether leakage current event is set or not.
The leakage current threshold can also be set through Accura 2300 LCD screen or communication. Threshold
via Accura 2300 are common to all Accura 2350s connected to Accura 2300. If you want to set different
threshold in Accura 2350 modules, you must set them individually through SET button on Accura 2350.