Accura 2300/2350 User Guide
Chapter 4 Accura 2300 Operation/Setup
ⓒ
2011 Rootech Inc. All Rights Reserved
Page 151
End Current
Current end event is generated when the measured current returns below the end current. Hysteresis exists
between start current and end current to prevent a large number of short events and minimum Hysteresis is
1%. In other words, end current can be configured at least 1% lower than the start current. If start current is
configured lower than end voltage, end current is automatically reconfigured 1% lower than start current.
Setup range
Description
0.0 - 998.0 % [default 98.0%]
End current percentage
Reference current for percentage is rating current for each Accura 2350.
Commonly applied to all Accura 2350s.
Current Delay Time
Current start event is generated when the measured current goes above start current and maintains upward
status for exceeding current delay time.
Setup range
Description
0, 1 - 999 sec [default 1 sec]
Current delay time[sec]
0 setup: Current delay time is 0.5-second.
Commonly applied to all Accura 2350s.
Leakage Current Event
When the leakage current event is set to on, the screens that configure start leakage current and leakage
current delay time are displayed. If the leakage current event is set to off, setup screen moves to demand
current event setup screen.
Setup range
Description
All.oFF[default]
Event off
All.on
Event on
no.SEL
Exit change mode to previous setup mode.
Commonly applied to all Accura 2350s.
Individual setup for each module can be done in each Accura 2350 module.
Start Leakage Current
Leakage current start event is generated when the measured leakage current goes above start leakage current
and maintains upward status for exceeding leakage current delay time.