Chapter 3 Accura 2350 Operation/Setup
Accura 2300/2350 User Guide
Page 100
ⓒ
2011 Rootech Inc. All Rights Reserved
Load Connection Setup
When Accura 2300 voltage connection is 3P3W, 3P4W and Accura 2350-3P three phase power measuring
module is used, it is possible to calculate with respect to the phases by specifying the number of loads. When
set to "3Ld", current/power is divided into 3-phase. If set to "2Ld", only the selected 2 phases are distributed. If
set to "1Ld", only the selected single phase is measured.
When the voltage connection is 1P2W or 1P3W, three-phase power measuring module automatically performs
the measurement according to the 1P2W, 1P3W setup, so this load connection setup is meaningless.
Item
Description
thC: through-hole Connection
3Ld [3-load, default]
3-phase load (
Δ
or
Υ
connection)
(Individual current/power calculation for three loads)
thC: through-hole Connection
2Ld [2-load]
line-to-line 2-load
(Individual current/power calculation for two loads)
thC: through-hole Connection
1Ld [single load]
line-to-line single load
(Individual current/power calculation for one load)
Phase single load
(Individual current/power calculation for one load)