Accura 2350-3PSC[1PSC, 1PSCSH] Split-core Power Measuring Module
Accura 2350-3PSC[1PSC, 1PSCSH] split-core power measuring module makes it possible to install without
power interruption by split-core structure.
Module
Function
Split-core three-phase
Split-core single-phase
Split-core single-phase
single-hole
7
Model
Minimum
Measurement
Measuring Range
[Accuracy guaranteed]
Three-phase
Accura 2350-3PSC-250A-105
1.67A
2.50A - 300A
Accura 2350-3PSC-125A-90
0.83A
1.25A - 150A
Accura 2350-3PSC-60A-75
0.40A
0.60A -
72A
Accura 2350-3PSC-CT5A-90
1
CT33mA
CT50mA - CT6A
2
Single-phase
Accura 2350-1PSC-250A-105
1.67A
2.50A - 300A
Accura 2350-1PSC-125A-60
0.83A
1.25A - 150A
Accura 2350-1PSC-60A-50
0.40A
0.60A -
72A
Single-phase
Accura 2350-1PSCSH-800A
0.80A
3.20A - 960A
single-hole
Accura 2350-1PSCSH-630A
0.63A
2.52A - 756A
Accura 2350-1PSCSH-400A
0.40A
1.60A - 480A
Measurement
Sampling/cycle for harmonic analysis
64
Sampling/cycle for RMS and power calculation
32
Measurement frequency range
50/60Hz, 42-69Hz
Current
±
0.5% RD
9
[
±
0.2% RD
8
]
Power, Energy
IEC62053-22 Class 0.5S[Class 0.2S
8
]
Communication
RS-485
3
2 ports[RJ12A, RJ12B]
4
Combination
Connected with Accura 2300[or 2350] by 6C telephone line
5,6
General
UL certification
UL61010-1
CE certification
EN61326-1, EN61326-2-1, EN61010-1
Power supply
Supplied from Accura 2300
1. If through-hole current exceeds 250A, Accura 2350-3PSC-CT5A-90 using external CT should be used.
2. Indicates CT secondary current input range.
3. Only for communication with Accura 2300[or 2350] connected by 6C telephone line.
4. There is no functional difference between types A and B in RJ12A and RJ12B.
5. Maximum 15 Accura 2350s can be connected to each port[RJ12-1, RJ12-2] of Accura 2300.
6. Packaged with device. Core conductor of 6C telephone line should be minimum 0.128mm
2
[26 AWG].
7. Split-core single-phase single-hole power measuring modules can be used in three-phases by installing one module per
phase [A, B, C] and grouping them. In the case of three-phase three-wire connection, it is possible to measure three-phases
only by installing two modules on phase A and phase C.
8. Split-core single-phase single-hole power measuring module meets current accuracy ± 0.2% RD error and power/energy
accuracy IEC62053-22 Class 0.2S
9. Split-core three[single]-phase power measuring modules can increase the maximum ± 1% error depending on the
penetration position of power cable