Chapter 3 Accura 2350 Operation/Setup
Accura 2300/2350 User Guide
Page 106
ⓒ
2011 Rootech Inc. All Rights Reserved
Accura 2350-1P[1PSC] Single-phase Power Measuring Module
Application Model
Model
Minimum
Measurement
Measuring Range
[Accuracy guaranteed
1, 2
]
Single-phase
Accura 2350-1P-250A-105
250mA
1.00A -
300A
Accura 2350-1P-125A-60
125mA
0.50A -
150A
Accura 2350-1P-100A-50
100mA
0.40A -
120A
Accura 2350-1P-60A-50
60mA
0.24A -
72A
Accura 2350-1P-50A-35
50mA
0.20A -
60A
Accura 2350-1P-30A-35
30mA
0.12A -
36A
Single-phase single-hole
Accura 2350-1PSH-50A-35
50mA
0.20A -
60A
Accura 2350-1PSH-30A-35
30mA
0.12A -
36A
Split-core single-phase
Accura 2350-1PSC-250A-105
1.67A
2.50A -
300A
Accura 2350-1PSC-125A-60
0.83A
1.25A -
150A
Accura 2350-1PSC-60A-50
0.40A
0.60A -
72A
1. Single-phase[single-phase single-hole] module meets ± 0.2% RD current accuracy and IEC62053-22 Class 0.5S
power/energy accuracy.
2. Split-core single-phase modules meet ± 0.5% RD current accuracy and IEC62053-22 Class 0.5S power/energy accuracy.
And these modules can increase the maximum ± 1% error depending on the penetration position of power cable.
Display Mode
Front Display
Display
ID
Accura 2350 Module ID
1
A/mA
Current unit[A or mA]
kW
Power unit
kWh
Energy unit
Load direction:
Load direction:
1. Module ID is divided as follows. All Accura 2350s are factory-assigned as Standby ID by default.
Module ID
ID
Description
Communication ID
ID 0 - 39
Able to communicate with Accura 2300.
Conflict ID
ID Duplication
Two or more IDs are the same Module ID, unable to communicate.
Standby ID
ID 255
Module ID for connection status recognition, unable to communicate.